D P M - C 5 0 1 L / C 5 0 2 O p e r a t i o n M a n u a l
3 - 4
_3
_3
3.2
Basic Checks
Items
Contents
General Check
Regularly check for losing of the fixing mount at the location where the power meter and
device are connected.
Guard against entrance of foreign objects, such as oil, water, or metal powder at the heat
dissipating holes. Guard against entrance of drill cut powders into the power meter.
Should the power meter be installed at a place present with harmful gas or dust, guard
against entrance of those matters into the meter.
Pre-operation
Check
(not supplied
with power)
Insulate the connecting spot of the wiring terminals.
Communications wiring should be done properly, or abnormal operations might result.
Check for presence of conducive and flammable objects, such as screws or metal pieces,
in the power meter.
Should electronic devices used near the power meter experience electromagnetic
interference, tune with instruments to reduce electromagnetic interference.
Check for correct voltage level for the power supplied to the power meter.
Pre-running
Check
(supplied with
power)
Check whether power indicator light is lit.
Check whether communication between every device is normal.
If there is any abnormal response from the power meter, contact your distributor or our
customer service center.
3.3
Wiring
3.3.1
Wiring Diagrams
To avoid electric shock, do not alter wiring when the power is on.
As there is no power switch on the power meter, be sure to install a breaker switch on the power cord for
the meter.
When measured voltage is higher than the rated specification for the device, use of an external potential
transformer (PT) is necessary.
When measured current is higher than the rated specification for the device, use of an external current
transformer (CT) is necessary.
Recommended wiring materials are shown below:
Connecting Terminals
Wire Diameters
Screw Turning Torque
Temperature rating
Operating power, RS-485, DI/DO
AWG 12 to 24
8.0 kgf-cm (0.8 N·m)
more than 70°C
Voltage and current measurement
AWG 12 to 24
8.0 kgf-cm (0.8 N·m)
more than 70°C
Содержание DPM-C501L
Страница 14: ...DPM C501L C502 Operation Manual 2 6 _2 2 4 Dimension Front Unit mm Back...
Страница 18: ...DPM C501L C502 Operation Manual 2 10 _2 MEMO...
Страница 26: ...DPM C501L C502 Operation Manual 3 8 _3 _3 MEMO...
Страница 71: ...DPM C501L C502 Operation Manual 5 34 _5 MEMO...
Страница 72: ...6 1 Chapter 6 Error Codes Table of Contents 6 1 Table of Error Codes 6 2 6...
Страница 74: ...A 1 Appendix A Accessories Table of Contents A 1 DCT1000 Series A 2 A 2 DCT2000 Series A 4 12 A...
Страница 79: ...DPM C501L C502 Operation Manual A 6 _A _1 MEMO...