C h a p t e r 3 I n s t a l l a t i o n
3 - 7
3_
3.3.3
Communication Characteristics
Communications Specifications:
Max. Communication
Distance
1200 m
Baud Rate
9600, 19200, 38400
Max. Connection
Number
32
Data Length
8
Communication
Protocols
MODBUS RTU
Parity
None, Odd, Even
Function Code
03, 06, 10,
FE (only available for
DPM-C502)
Stop Bit
1
Use two-wire cables for RS-485 communication.
The D+ communication terminal for all devices should be connected on the same twisted pair cable. The
D- terminals should be connected on the other twisted pair cable. The insulation net is grounded. The
device on the end terminal needs to have terminal resistor installed on it.
Use cables with a diameter of 14 to 24 AWG.