DPM-C501L/C502 Operation Manual
2-2
_2
2.1
Electrical Characteristics
Input
Voltage
Connection
1PH2W, 1 CT
3PH3W, Δ connection, 3 CT, 2 PT
1PH3W, 2 CT
3PH4W, Y connection, 3 CT, No PT
3PH3W, Δ connection, 3 CT, No PT
3PH4W, Y connection, 3 CT, 3 PT
3PH3W, Δ connection, 2 CT, No PT
3PH4W, Y connection, 2 CT, 3 PT
Rated Voltage
Line voltage: 35 to 690 VAC (L-L)
Phase voltage: 20 to 400 VAC (L-N)
Rated Current
1A / 5A
Frequency
50/60 Hz
Harmonic
DPM-C501L
Total voltage / current harmonic
distortion in average
DPM-C502
Individual voltage / current harmonic
distortion in average
Voltage Input
Measuring Category: CAT III
Alarm
Set up multi-level alarms
10 multi-level alarms
Maximum /
Minimum
15/15 types
With timestamp
Power
Operating range
80 to 265 VAC (max. power: 4.6W
)
100 to 300 VDC
Frequency
Operating frequency
50/60 Hz
Measurement Accuracy
Electric quantities
Voltage, current
± 0.5 %
Electric
energy
Real power
± 0.5 %
Real power, reactive
power, apparent power
± 0.5 %
Reactive
power
± 0.5 %
Power factor
± 0.5 %
Total Current Harmonic
Distortion
± 1 %
Real power
± 0.5 %
Total Voltage Harmonic
Distortion
± 1 %
Reactive power
± 0.5 %
Frequency
± 0.5 %
Apparent power
± 0.5 %
Harmonic
± 1 %
Содержание DPM-C501L
Страница 14: ...DPM C501L C502 Operation Manual 2 6 _2 2 4 Dimension Front Unit mm Back...
Страница 18: ...DPM C501L C502 Operation Manual 2 10 _2 MEMO...
Страница 26: ...DPM C501L C502 Operation Manual 3 8 _3 _3 MEMO...
Страница 71: ...DPM C501L C502 Operation Manual 5 34 _5 MEMO...
Страница 72: ...6 1 Chapter 6 Error Codes Table of Contents 6 1 Table of Error Codes 6 2 6...
Страница 74: ...A 1 Appendix A Accessories Table of Contents A 1 DCT1000 Series A 2 A 2 DCT2000 Series A 4 12 A...
Страница 79: ...DPM C501L C502 Operation Manual A 6 _A _1 MEMO...