D P M - C 5 0 1 L / C 5 0 2 O p e r a t i o n M a n u a l
4 - 4
_4
7.
When the option starts blinking, you can use UP and DOWN keys to select the parity you need.
8.
Press NEXT key to confirm the setting.
Note: You can go back to the previous setting item by pressing BACK key anytime, whether you have
completed or canceled the setting.
4.2.3
System Setup (SYS)
Wiring methods (WR): options are one-phase two-wire (1PH2W), one-phase three-wire (1PH3W),
three-phase three-wire (3PH3W), and three-phase four-wire (3PH4W); default: three-phase four-wire.
Number of current transformers (CT): options are 1, 2 and 3; default: 3.
Number of potential transformers (PT): options are 0, 2 and 3; default: 3.
Steps:
1.
Press NEXT key till the option starts blinking.
2.
Use UP and DOWN keys to select the wiring method.
3.
Press NEXT key to confirm the setting and start to set the next setting, the number of current
transformers (CT).
4.
When the option starts blinking, you can use UP and DOWN keys to select the number of current
transformers you need.
5.
Press NEXT key to confirm the setting and start to set the next setting, the number of potential
transformers (PT).
6.
When the option starts blinking, you can use UP and DOWN keys to select the number of potential
transformers you need.
7.
Press NEXT key to confirm the setting.
Note: You can go back to the previous setting item by pressing BACK key anytime, whether you have
completed or canceled the setting.
4.2.4
Current Transformer Setup (CT)
Ampere for the primary-side current transformer: ranging from 1 to 9999 A; default: 5 A.
Ampere for the secondary-side current transformer: options are 1 and 5 A; default 5 A.
Steps:
1.
Press NEXT key till the first digit starts blinking
2.
Use UP and DOWN keys to select the number for the primary-side current transformer.
3.
Press NEXT key to confirm the setting and start to set the next number for the primary-side current
transformer.
4.
Repeat steps 2-3 till you complete the settings of the 4 digit number for the primary-side current
transformer. Press NEXT key to set up the secondary-side current transformer.
5.
When the option starts blinking, you can use UP and DOWN keys to select the number of the
Содержание DPM-C501L
Страница 14: ...DPM C501L C502 Operation Manual 2 6 _2 2 4 Dimension Front Unit mm Back...
Страница 18: ...DPM C501L C502 Operation Manual 2 10 _2 MEMO...
Страница 26: ...DPM C501L C502 Operation Manual 3 8 _3 _3 MEMO...
Страница 71: ...DPM C501L C502 Operation Manual 5 34 _5 MEMO...
Страница 72: ...6 1 Chapter 6 Error Codes Table of Contents 6 1 Table of Error Codes 6 2 6...
Страница 74: ...A 1 Appendix A Accessories Table of Contents A 1 DCT1000 Series A 2 A 2 DCT2000 Series A 4 12 A...
Страница 79: ...DPM C501L C502 Operation Manual A 6 _A _1 MEMO...