D P M - C 5 0 1 L / C 5 0 2 O p e r a t i o n M a n u a l
5 - 2
_5
5.1
Advanced Features
DPM-C501L: Harmonic measurements, including voltage and current harmonics.
DPM-C502: Harmonic measurements, including voltage and current harmonics. Features such as 1-31 levels
of harmonic measurements, data log, time of use measurement, demand value measurement are also included.
For data log feature, you can store data for up to 7 days and the minimum interval can be set to 1 minute. For
the time of use feature, up to 4 groups can be set. Refer to parameters below for more details.
5.2
Overview of Parameters
MODBUS
Address
Item
Range
Data
Type
Unit
Data
Size
(byte)
Read (R) /
Write (W)
Hex
Modicom
Format
0. System Parameters: 0001 - 00FF
1
40002
Present date
Year: 00-99
Month: 1-12
byte
Year,
Month
2
R/W
2
40003
Date: 1-31
Week: Sun-Sat
byte
Date,
Week
2
R/W
3
40004
Present time
Hour: 00-23
Minute: 00-59
byte
Hour,
Minute
2
R/W
4
40005
Second: 00-59
word Second
2
R/W
5
40006 Meter Constant
3200
uint
P/kWh
2
R
6
40007 Meter Model
0: None
6: C501L
12: C502
word
2
R
7
40008
Total running time of the
meter
Day: 0-65535
uint
Day
2
R
8
40009
Hour: 00-23
Minute: 00-59
byte
Hour,
Minute
2
R
Содержание DPM-C501L
Страница 14: ...DPM C501L C502 Operation Manual 2 6 _2 2 4 Dimension Front Unit mm Back...
Страница 18: ...DPM C501L C502 Operation Manual 2 10 _2 MEMO...
Страница 26: ...DPM C501L C502 Operation Manual 3 8 _3 _3 MEMO...
Страница 71: ...DPM C501L C502 Operation Manual 5 34 _5 MEMO...
Страница 72: ...6 1 Chapter 6 Error Codes Table of Contents 6 1 Table of Error Codes 6 2 6...
Страница 74: ...A 1 Appendix A Accessories Table of Contents A 1 DCT1000 Series A 2 A 2 DCT2000 Series A 4 12 A...
Страница 79: ...DPM C501L C502 Operation Manual A 6 _A _1 MEMO...