C h a p t e r 1 2 Tr o u b l e s h o o t i n g
1 2 - 6 5
Error
code
Description
CPU
Status
LED indicator status
ERROR
BUS
FAULT
16#1402
The actual arrangement of the I/O modules is not
consistent with the module table. (SM9)
Stop
Keep
ON
16#1403
An error occurs when the data is read from the module.
(SM9)
Stop
Keep
ON
16#1405
The setting parameter of the module is not found.
(SM9)
Stop
Keep
ON
16#1407
A communication error occurs when the data is
accessed through the auxiliary processor. (SM9)
Continue
ON
Keep
16#1409
The extension backplane is disconnected. (SM9)
Stop
Keep
ON
16#140A
The communication with the extension backplane is
incorrect. (SM9)
Stop
Keep
ON
16#140B
The number of network modules exceeds the limit.
(SM9)
Stop
Keep
ON
16#140C
The checksum of the high-speed data exchange is
incorrect. (SM9)
Stop
Keep
ON
16#140D
The ID of the actual power supply module is not the
same as the ID of the power supply module set in
HWCONFIG. (SM9)
Stop
Keep
ON
16#140E
The amount of data exchanged at a high speed
exceeds the maximum amount supported. (SM10)
Stop
Keep
ON
16#140F
High-speed data exchange error (SM11)
Stop
Keep
ON
16#1801
There is no interrupt service routine in the CPU
module.
Continue
Keep
Keep
16#2000
There is no END in the program in the PLC. (SM5)
Stop
Blinking
Keep
16#2001
The program is incorrect. There is a syntax error.
(SM5)
Stop
Blinking
Keep
16#2002
GOEND is used incorrectly. (SM5)
Stop
Blinking
Keep
16#2003
The devices used in the program exceed the range.
(SM0/SM5)
Self-defined
Blinking
Keep
16#2004
The part of the program specified by the label used in
CJ/JMP is incorrect, or the label is used repeatedly.
(SM0/SM5)
Stop
Blinking
Keep
16#2005
The N value used in MC is not the same as the
corresponding N value used in MCR, or the number of
N values used in MC is not the same as the number of
N values used in MCR. (SM5)
Stop
Blinking
Keep
16#2006
The N values used in MC do not start from 0, or the N
values used in MC are not continuous. (SM5)
Stop
Blinking
Keep
16#2007
The operands used in ZRST are not used properly.
(SM5)
Stop
Blinking
Keep
16#200A
Invalid instruction (SM5)
Stop
Blinking
Keep
16#200B
The operand
n
or the other constant operands exceed
the range. (SM0/SM5)
Self-defined
Blinking
Keep
16#200C
The operands overlap. (SM0/SM5)
Self-defined
Blinking
Keep
16#200D
An error occurs when the binary number is converted
into the binary-coded decimal number. (SM0/SM5)
Self-defined
Blinking
Keep
16#200E
The string does not end with 0x00. (SM0/SM5)
Self-defined
Blinking
Keep
16#200F
The instruction does not support the modification by an
index register. (SM5)
Stop
Blinking
Keep
Содержание AH500 series
Страница 35: ...AH500 Hardware and Operation Manual 2 2 2 12 2 Profiles 2 117 2 12 3 Dimensions 2 118 ...
Страница 153: ...AH500 Hardware and Operation Manual 2 120 MEMO ...
Страница 167: ...AH500 Hardware and Operation Manual 3 14 MEMO ...
Страница 183: ...AH500 Hardware and Operation Manual 4 16 2 Pull up the clip Type I Type II 3 Remove the terminal block Type I Type II ...
Страница 343: ...AH500 Hardware and Operation Manual 6 38 MEMO ...
Страница 361: ...AH500 Hardware and Operation Manual 7 18 MEMO ...
Страница 403: ...Chapter 8 Hardware Configuration 8 42 MEMO ...
Страница 412: ...Chapter 9 Network Configuration 9 9 ...
Страница 445: ...AH500 Hardware and Operation Manual 9 42 MEMO ...
Страница 552: ...Chapter 12 Troubleshooting 12 3 12 1 3 Troubleshooting Procedure ...
Страница 649: ...AH500 Hardware and Operation Manual A 8 ...
Страница 657: ...AH500 Hardware and Operation Manual A 16 MEMO ...
Страница 658: ...B 1 Appendix B Device Addresses Table of Contents B 1 Device Addresses B 2 ...
Страница 663: ...AH500 Hardware and Operation Manual C 4 MEMO ...
Страница 681: ...AH500 Hardware and Operation Manual 3 14 MEMO ...