A H 5 0 0 H a r d w a r e a n d O p e r a t i o n M a n u a l
11 - 6 8
The
Item 1
window is described below.
Enable
If users want to make the PLC execute the data exchange, they have to select the
Enable
checkbox. If the
users want to stop the data exchange temporarily, they can leave the
Enable
checkbox unselected.
IP Address
Users have to type the IP address of the slave to which the PLC will connect in the
IP Address
box.
The Shortest Update Cycle (ms)
Users have to set the shortest cycle of updating the data exchange. A millisecond is a unit of time. When
the data exchange is executed, it is updated at specific intervals. However, if the data exchange is
prolonged due to network congestion or other reasons, it will be updated according to the actual situation.
Connection Timeout (ms)
Users can set the longest time that is allowed to elapse before the data exchange is executed. A
millisecond is a unit of time. If the data exchange is not executed after the longest time set elapses, a
connection timeout will occur. The PLC still tries to connect to the slave station selected at specific
intervals. Once the PLC connects to the slave station selected, the data exchange will be executed.
Support read/write synchronization (Function code 0x17)
If the slave to which the PLC will connect can complete reading and writing simultaneously (Modbus
function code 0x17), users can select the
Support read/write synchronization (Function code 0x17)
checkbox. After the
Support read/write synchronization (Function code 0x17)
checkbox is selected,
the PLC will read data and write data simultaneously, and the efficiency in exchanging data will increase.
Device Type
Users can select the model of the slave to which the PLC will connect in the
Device Type
drop-down list
box. They can select a standard Modbus TCP device or a Delta PLC. If they select a Delta PLC, they can
use the registers in the Delta PLC when they set data blocks. When selecting a 3
rd
party device, they can
select Modbus Register Hex from the Remote Start Address (Hex) drop-down list and define a
hexadecimal 4-digit Modbus absolute positon.
Input
Users can set the register in which the data read will be stored in the
Local Start Address
box. The
register set can only be a D device (not limited to AH500 advanced CPU series: AHCPU501/511/521/531).
The users can set the register whose contents will be read in the
Remote Start Address
box. The register
and the address which can be set depend on the device type selected in the
Device Type
drop-down list
box. The users can set the quantity of data which will be read in the
Quantity
box. For AH500 basic CPU
series (AHCPU500/510/520/530), the unit used depends on the remote register type selected. 100 words
(1600 bits) at most can be read. However, if the slave to which the PLC will connect is an AH500 series
CPU module, 400 words (6400 bits) at most can be read. As for AH500 advanced CPU series
(AHCPU501/511/521/531), users can select the register type according to the requirements.
Output
Users can set the register whose contents will be written in the
Local Start Address
box. The register set
can only be a D device (not limited to AH500 advanced CPU series: AHCPU501/511/521/531). The users
can set the register into which data will be written in the
Remote Start Address
box. The register and the
address which can be set depend on the device type selected in the
Device Type
drop-down list box. The
users can set the quantity of data which will be written in the
Quantity
box. For AH500 basic CPU series
(AHCPU500/510/520/530), the unit used depends on the remote register type selected. 100 words (1600
bits) at most can be written. However, if the slave to which the PLC will connect is an AH500 series CPU
module, 400 words (6400 bits) at most can be written. As for AH500 advanced CPU series
(AHCPU501/511/521/531), users can select the register type according to the requirements.
When users set a data exchange block, the local register set can only be a word device, and the remote
register set can be a bit device. If the remote register set is a bit device, the device number of the remote
register does not need to end with 0. For example, the remote register set can be D0.3. If the data which
Содержание AH500 series
Страница 35: ...AH500 Hardware and Operation Manual 2 2 2 12 2 Profiles 2 117 2 12 3 Dimensions 2 118 ...
Страница 153: ...AH500 Hardware and Operation Manual 2 120 MEMO ...
Страница 167: ...AH500 Hardware and Operation Manual 3 14 MEMO ...
Страница 183: ...AH500 Hardware and Operation Manual 4 16 2 Pull up the clip Type I Type II 3 Remove the terminal block Type I Type II ...
Страница 343: ...AH500 Hardware and Operation Manual 6 38 MEMO ...
Страница 361: ...AH500 Hardware and Operation Manual 7 18 MEMO ...
Страница 403: ...Chapter 8 Hardware Configuration 8 42 MEMO ...
Страница 412: ...Chapter 9 Network Configuration 9 9 ...
Страница 445: ...AH500 Hardware and Operation Manual 9 42 MEMO ...
Страница 552: ...Chapter 12 Troubleshooting 12 3 12 1 3 Troubleshooting Procedure ...
Страница 649: ...AH500 Hardware and Operation Manual A 8 ...
Страница 657: ...AH500 Hardware and Operation Manual A 16 MEMO ...
Страница 658: ...B 1 Appendix B Device Addresses Table of Contents B 1 Device Addresses B 2 ...
Страница 663: ...AH500 Hardware and Operation Manual C 4 MEMO ...
Страница 681: ...AH500 Hardware and Operation Manual 3 14 MEMO ...