C h a p t e r 1 2 Tr o u b l e s h o o t i n g
1 2 - 2 5
Error
Code
Description
Solution
16#E299
The network module heart beat of the
control mode CPU on the main backplane
slot 9 cannot be detected.
1. Make sure the network cables of the network
modules on the main backplane slot 9 are
well-connected both on the control mode CPU
and standby mode CPU.
2. If the network module’s network cable of the
control mode CPU on the main backplane slot 9
is connected to the network port 1, the network
module’s network cable of the standby mode
CPU on the main backplane slot 9 must be
connected to the network port 1 as well.
3. Mare sure the network modules of the control
mode CPU and the standby mode CPU on the
main backplane slot 9 are on the same physical
network.
16#E29A
The network module heart beat of the
control mode CPU on the main backplane
slot 10 cannot be detected.
1. Make sure the network cables of the network
modules on the main backplane slot 10 are
well-connected both on the control mode CPU
and standby mode CPU.
2. If the network module’s network cable of the
control mode CPU on the main backplane slot
10 is connected to the network port 1, the
network module’s network cable of the standby
mode CPU on the main backplane slot 10 must
be connected to the network port 1 as well.
3. Mare sure the network modules of the control
mode CPU and the standby mode CPU on the
main backplane slot 10 are on the same physical
network.
16#E29B
The network module heart beat of the
control mode CPU on the main backplane
slot 11 cannot be detected.
1. Make sure the network cables of the network
modules on the main backplane slot 11 are
well-connected both on the control mode CPU
and standby mode CPU.
2. If the network module’s network cable of the
control mode CPU on the main backplane slot
11 is connected to the network port 1, the
network module’s network cable of the standby
mode CPU on the main backplane slot 11 must
be connected to the network port 1 as well.
3. Mare sure the network modules of the control
mode CPU and the standby mode CPU on the
main backplane slot 11 are on the same physical
network.
16#E2A0
The IP detection on the network module
installed on the main backplane slot 0 has
NOT been executed.
After the execution of IP detection is complete.
16#E2A1
The IP detection on the network module
installed on the main backplane slot 1 has
NOT been executed.
After the execution of IP detection is complete.
16#E2A2
The IP detection on the network module
installed on the main backplane slot 2 has
NOT been executed.
After the execution of IP detection is complete.
16#E2A3
The IP detection on the network module
installed on the main backplane slot 3 has
NOT been executed.
After the execution of IP detection is complete.
Содержание AH500 series
Страница 35: ...AH500 Hardware and Operation Manual 2 2 2 12 2 Profiles 2 117 2 12 3 Dimensions 2 118 ...
Страница 153: ...AH500 Hardware and Operation Manual 2 120 MEMO ...
Страница 167: ...AH500 Hardware and Operation Manual 3 14 MEMO ...
Страница 183: ...AH500 Hardware and Operation Manual 4 16 2 Pull up the clip Type I Type II 3 Remove the terminal block Type I Type II ...
Страница 343: ...AH500 Hardware and Operation Manual 6 38 MEMO ...
Страница 361: ...AH500 Hardware and Operation Manual 7 18 MEMO ...
Страница 403: ...Chapter 8 Hardware Configuration 8 42 MEMO ...
Страница 412: ...Chapter 9 Network Configuration 9 9 ...
Страница 445: ...AH500 Hardware and Operation Manual 9 42 MEMO ...
Страница 552: ...Chapter 12 Troubleshooting 12 3 12 1 3 Troubleshooting Procedure ...
Страница 649: ...AH500 Hardware and Operation Manual A 8 ...
Страница 657: ...AH500 Hardware and Operation Manual A 16 MEMO ...
Страница 658: ...B 1 Appendix B Device Addresses Table of Contents B 1 Device Addresses B 2 ...
Страница 663: ...AH500 Hardware and Operation Manual C 4 MEMO ...
Страница 681: ...AH500 Hardware and Operation Manual 3 14 MEMO ...