A H 5 0 0 H a r d w a r e a n d O p e r a t i o n M a n u a l
1 2 - 4 8
12.3.2
Troubleshooting for AH02HC-5A/AH04HC-5A
Error
code
Description
Remedy
16#A001
The linear accumulation in
channel 0 exceeds the range.
To clear the linear accumulation, users need to set bit 1 in
CR0 to ON by means of FROM/TO.
16#A002
The scale set for channel 0
exceeds the range.
Check the module parameter in HWCONFIG.
The scale set for channel 0 should be in the range of 0 to
32767.
16#A003
The number of cycles set for
channel 0 exceeds the range.
Check the module parameter in HWCONFIG.
The number of cycles set for channel 0 should be in the
range of 2 to 60.
16#A004
The comparison value set for
channel 0 exceeds the range.
Check the module parameter in HWCONFIG.
The comparison value set for channel 0 should be in the
range of -999999999 to 999999999.
16#A005
A limit value set for channel 0 is
incorrect.
Check the module parameter in HWCONFIG.
A limit value of set for channel 0 should be in the range of
-200000 to 200000.
16#A006
The interrupt number set for
channel 0 exceeds the range.
Check the module parameter in HWCONFIG.
The interrupt number set for channel 0 should be in the
range of 0 to 31.
16#A011
The linear accumulation in
channel 1 exceeds the range.
To clear the linear accumulation, users need to set bit 1 in
CR28 to ON by means of FROM/TO.
16#A012
The scale set for channel 1
exceeds the range.
Check the module parameter in HWCONFIG.
The scale set for channel 1 should be in the range of 0 to
32767.
16#A013
The number of cycles set for
channel 1 exceeds the range.
Check the module parameter in HWCONFIG.
The number of cycles set for channel 1 should be in the
range of 2 to 60.
16#A014
The comparison value set for
channel 1 exceeds the range.
Check the module parameter in HWCONFIG.
The comparison value set for channel 1 should be in the
range of -999999999 to 999999999.
16#A015
A limit value set for channel 1 is
incorrect.
Check the module parameter in HWCONFIG.
A limit value of set for channel 1 should be in the range of
-200000 to 200000.
16#A016
The interrupt number set for
channel 1 exceeds the range.
Check the module parameter in HWCONFIG.
The interrupt number set for channel 1 should be in the
range of 0 to 31.
16#A021
The linear accumulation in
channel 2 exceeds the range.
To clear the linear accumulation, users need to set bit 1 in
CR56 to ON by means of FROM/TO.
16#A022
The scale set for channel 2
exceeds the range.
Check the module parameter in HWCONFIG.
The scale set for channel 2 should be in the range of 0 to
32767.
16#A023
The number of cycles set for
channel 2 exceeds the range.
Check the module parameter in HWCONFIG.
The number of cycles set for channel 2 should be in the
range of 2 to 60.
16#A024
The comparison value set for
channel 2 exceeds the range.
Check the module parameter in HWCONFIG.
The comparison value set for channel 2 should be in the
range of -999999999 to 999999999.
16#A025
A limit value set for channel 2 is
incorrect.
Check the module parameter in HWCONFIG.
A limit value of set for channel 2 should be in the range of
-200000 to 200000.
16#A026
The interrupt number set for
channel 2 exceeds the range.
Check the module parameter in HWCONFIG.
The interrupt number set for channel 2 should be in the
range of 0 to 31.
Содержание AH500 series
Страница 35: ...AH500 Hardware and Operation Manual 2 2 2 12 2 Profiles 2 117 2 12 3 Dimensions 2 118 ...
Страница 153: ...AH500 Hardware and Operation Manual 2 120 MEMO ...
Страница 167: ...AH500 Hardware and Operation Manual 3 14 MEMO ...
Страница 183: ...AH500 Hardware and Operation Manual 4 16 2 Pull up the clip Type I Type II 3 Remove the terminal block Type I Type II ...
Страница 343: ...AH500 Hardware and Operation Manual 6 38 MEMO ...
Страница 361: ...AH500 Hardware and Operation Manual 7 18 MEMO ...
Страница 403: ...Chapter 8 Hardware Configuration 8 42 MEMO ...
Страница 412: ...Chapter 9 Network Configuration 9 9 ...
Страница 445: ...AH500 Hardware and Operation Manual 9 42 MEMO ...
Страница 552: ...Chapter 12 Troubleshooting 12 3 12 1 3 Troubleshooting Procedure ...
Страница 649: ...AH500 Hardware and Operation Manual A 8 ...
Страница 657: ...AH500 Hardware and Operation Manual A 16 MEMO ...
Страница 658: ...B 1 Appendix B Device Addresses Table of Contents B 1 Device Addresses B 2 ...
Страница 663: ...AH500 Hardware and Operation Manual C 4 MEMO ...
Страница 681: ...AH500 Hardware and Operation Manual 3 14 MEMO ...