Appendix
Installation Manual
62
Output Voltage Regulation
< 10%, at dynamic; Recovering within tolerance in 100 ms
Crest Factor
2.0 @ rated power
Max Altitude
3,000 m (9,843 ft)
Thermal derating above 2,000 m (6,561.68 ft.)
Environment
Operating Temperature
≤
2,000 m: -25 ~ 60ºC (-13 ~ 140ºF), derating > 50ºC (3%/ºC)
> 2,000 m: -25 ~ 40ºC (-13 ~ 104ºF),
Storage Temperature
-25 ~ 70ºC (-13 ~ 158ºF)
Humidity
0 to 95% RH, no-condensing
Cooling
Fan cooled, speed controlled and alarmed signal
Pollution Degree
3
Acoustic Noise
< 72 dBA @ 1 m (3.3 ft)
IP Degree
IP55
Interface & Communication
Digital I/O
3 x Input, 0 - 24 V
2 x Output relays
User Interface
4.9 inch LCD screen with push button, Fault LEDs
Emergency Stop
Local EPO button & remote control
Communication
RS-485 / Modbus RTU, CAN
System Characteristic
Peak Efficiency
97.2%
Sleep Mode Loss
< 25 W
Operation Mode
Demand charge management (Power Dispatch)
Load shifting for Time-of-Use saving
Power quality improvement (P-Q Control, Frequency
Regulation)
Emergency backup power
Dimensions (W x D x H)
(excl. Package)
600 mm x 800 mm x 1,766 mm / 23.6 in x 31.5 in x 69.5 in
Net Weight (excl. Package)
310 kg / 683 lbs
Standard Compliance
Certificate
IEC 62477-1, VDE-AR-N 4105, AS 62040.1.1,
AS/NZS 4777.2, IEC 61000-6-2/-4
Applicable Battery Chemistry
Lithium-ion, lead-acid, flow battery
Table 14: Technical Specifications of Delta 100kW PCS (Continued)
Item
Description
Содержание 100kW PCS
Страница 1: ...100kW Power Conditioning System PCS Installation Manual Version 1 0 0...
Страница 3: ...Installation Manual ii Warranty 60 Appendix 61 Specifications 61 Glossary 63 Screw Torque Table 65...
Страница 26: ...Installation Installation Manual 22 12 Repeat for the rear panel Figure 20 Closing a Rear Panel...
Страница 38: ...Installation Installation Manual 34 3 Repeat for the rear panel Figure 35 Closing a Rear Panel...