Wiring Instructions
Installation Manual
42
Communication and I/O Wire Sizing and Ratings
Here are the requirements for the communication and I/O wires:
Preparation of Cables
This section describes how to prepare the cable prepare the corresponding cables and wires to meet
the specified requirements, see “Wire Sizing and Ratings” on page 41.
The following items require preparation:
2 x 1000V, 53.49 mm
2
cables for DC (battery) connection
6 x 600V or greater, 53.49 ~ 33.62 mm
2
cables for AC connection
1 x 600V or greater, 53.49 ~ 26.67 mm
2
cables for grounding
2 x 2-hole cable lugs (attached in the accessory kit) for grounding cable
1 x 15-pin green connector (enclosed in the accessory kit)
2 x 6-pin green connector (enclosed in the accessory kit)
1 x 2-pin green connector (enclosed in the accessory kit)
1 x 3-pin green connector (enclosed in the accessory kit)
3 x RJ45 connector
Table 5: Communication and I/O Wire Sizing and Ratings
Cable Type
Solid Copper Conductor
Voltage Rating
600 Volts or greater
Temperature
70°C or greater
Gauge
1.32 mm
2
Quantity
The following connectors, enclosed in accessory kit:
8 for CNJ3, 15-pin connector
2 for CNJ5, 2-pin connector
5 for CNJ13, 6-pin connector
6 for CNJ1, 6-pin connector
3 shielded network cables for CNJ11, CNJ12, and X1
CNJ7 (optional)
Note:
A RJ45 communication terminal resistor is inserted in CNJ11 (default). In parallel PCS
installation, the communication terminal resistor is installed in the last PCS.
Note:
Wiring must comply with the IEC standard and local regulations.
Содержание 100kW PCS
Страница 1: ...100kW Power Conditioning System PCS Installation Manual Version 1 0 0...
Страница 3: ...Installation Manual ii Warranty 60 Appendix 61 Specifications 61 Glossary 63 Screw Torque Table 65...
Страница 26: ...Installation Installation Manual 22 12 Repeat for the rear panel Figure 20 Closing a Rear Panel...
Страница 38: ...Installation Installation Manual 34 3 Repeat for the rear panel Figure 35 Closing a Rear Panel...