Appendix
Installation Manual
61
Appendix
Specifications
Table 14: Technical Specifications of Delta 100kW PCS
Item
Description
Grid-tied Operation
Rated Grid Voltage
400 Vac, 3 phase 3 wire
Grid Voltage Range
320 to 440 Vac (VDE-AR-N4105)
312 to 450 Vac (AS/NZS 4777.2)
Rated Grid Frequency
50 Hz
Frequency Range
47.5 to 51.5 Hz (VDE-AR-N4105)
47 to 52 Hz (AS/NZS 4777.2, Australia)
45 to 52 Hz (AS/NZS 4777.2, New Zealand)
Rated AC Power
100 kVA
Rated AC Current
144.3 A
Max. Continuous AC Current
160.4 Arms
Current THD
< 3% at rated power (VDE-AR-N4105 and AS/NZS 4777.2
Compliant)
Power Factor
-1 to 1, continuously adjustable
Charging-discharging Transfer Time < 100 ms (±90% rated power)
Power Response Time
< 40 ms (0~100% rated power)
Battery Input Performance
DC Voltage Range
750 to 1,000 Vdc
Rated DC Voltage
900 Vdc
Rated Discharge Power
103 kW
Rated Charge Power
97 kW
Max. Discharge DC Current
137.3 A (103 kW @ 750 Vdc)
Max. Charge DC Current
129.3A (97 kW @ 750 Vdc)
Standalone Mode Performance
Rated Output Voltage
400 Vac, 3P3W (In 3P4W case, extra Dyn transformer
needed)
Rated Output Power
100 kVA/100 kW
Rated Output Current
144.3 A
Rated Output Frequency
50 Hz ± 1%
Power Factor
0.8 to 1
Output Voltage Accuracy
1%
Voltage Symmetry
± 1%, @ 100% linear balanced load
Output Voltage THD
< 3% @ 12.5 ~ 100% liner load
< 5% @ 12.5 ~ 100% non-liner load (Crest factor
≤
2.0)
Содержание 100kW PCS
Страница 1: ...100kW Power Conditioning System PCS Installation Manual Version 1 0 0...
Страница 3: ...Installation Manual ii Warranty 60 Appendix 61 Specifications 61 Glossary 63 Screw Torque Table 65...
Страница 26: ...Installation Installation Manual 22 12 Repeat for the rear panel Figure 20 Closing a Rear Panel...
Страница 38: ...Installation Installation Manual 34 3 Repeat for the rear panel Figure 35 Closing a Rear Panel...