- 67 -
Address Type
Holding Register description
AP ED RE AL
50 SW
Lower alarm threshold for
TEMPERATURE
with
NTC10K
sensor of
channel
3
in the set measurement unit (x10).
9
51 SW
Higher alarm threshold for temperature with NTC10K sensor of
channel 3 in the set measurement unit (x10).
9
56 SW
D
IFFERENTIAL PRESSURE
lower alarm threshold for range
r3
in the
set measurement unit (the multiplier depends on the set unit).
9
57 SW
Differential pressure higher alarm threshold for range r3 in the
set measurement unit (multiplier depends on the set unit).
9
60 SW
D
IFFERENTIAL PRESSURE
lower alarm threshold for ranges
r1
and
r2
in the set measurement unit (the multiplier depends on the
set unit).
9
61 SW
Differential pressure higher alarm threshold for ranges r1 and r2
in the set measurement unit (the multiplier depends on the set
unit).
9
62 SW
D
IFFERENTIAL PRESSURE
lower alarm threshold for range
r4
in the
set measurement unit (the multiplier depends on the set unit).
9
63 SW
Differential pressure higher alarm threshold for range r4 in the
set measurement unit (the multiplier depends on the set unit).
9
64 SW
Lower alarm threshold for
TEMPERATURE
with
Pt100
sensor of
HP3517E… probe
in the set measurement unit (x10).
9
65 SW
Higher alarm threshold for temperature with Pt100 sensor of
HP3517E… probe
in the set measurement unit (x10).
9
68 SW
UVA
IRRADIANCE
lower alarm threshold in mW/m
2
.
9
69
SW UVA irradiance higher alarm threshold in mW/m
2
.
9
70 SW
P
ROPORTION OF
UV
PRESENT
lower alarm threshold in
µW/lumen.
9
71 SW
Proportion of UV present higher alarm threshold in
µW/lumen.
9
Measurement alarm thresholds for configurable inputs
1000 +
200
x
(
N
-1) SW
Lower alarm threshold for
TEMPERATURE
with
2-wire Pt100
sensor of channel
N
in the set measurement unit (x10).
9
1001 +
200
x
(
N
-1) SW
Higher alarm threshold for temperature with 2-wire Pt100 sen-
sor of channel
N
in the set measurement unit (x10).
9
1002 +
200
x
(
N
-1) SW
Lower alarm threshold for
TEMPERATURE
with
3-wire Pt100
sensor of channel
N
in the set measurement unit (x10).
9
1003 +
200
x
(
N
-1) SW
Higher alarm threshold for temperature with 3-wire Pt100 sen-
sor of channel
N
in the set measurement unit (x10).
9
1004 +
200
x
(
N
-1) SW
Lower alarm threshold for
TEMPERATURE
with
4-wire Pt100
sensor of channel
N
in the set measurement unit (x10).
9
1005 +
200
x
(
N
-1) SW
Higher alarm threshold for temperature with 4-wire Pt100 sen-
sor of channel
N
in the set measurement unit (x10).
9
1006 +
200
x
(
N
-1) SW
Lower alarm threshold for
TEMPERATURE
with
2-wire Pt1000
sensor of channel
N
in the set measurement unit (x10).
9
1007 +
200
x
(
N
-1) SW
Higher alarm threshold for temperature with 2-wire Pt1000
sensor of channel
N
in the set measurement unit (x10).
9
1008 +
200
x
(
N
-1) SW
Lower alarm threshold for
TEMPERATURE
with
3-wire Pt1000
sensor of channel
N
in the set measurement unit (x10).
9
1009 +
200
x
(
N
-1) SW
Higher alarm threshold for temperature with 3-wire Pt1000
sensor of channel
N
in the set measurement unit (x10).
9
1010 +
200
x
(
N
-1) SW
Lower alarm threshold for
TEMPERATURE
with
4-wire Pt1000
sensor of channel
N
in the set measurement unit (x10).
9
1011 +
200
x
(
N
-1) SW
Higher alarm threshold for temperature with 4-wire Pt1000
sensor of channel
N
in the set measurement unit (x10).
9
1012 +
200
x
(
N
-1) SW
Lower alarm threshold for
TEMPERATURE
with
TC_K
sensor of
channel
N
in the set measurement unit (x10).
9