- 60 -
TAB. 11.2: Discrete Inputs
– Read-only parameters
Address Type
Discrete Input description
AP ED RE AL
0 b
If 1, the device is subjected to RF interference due to the
transmission of more covering repeaters.
9
9
9
1
b
If 1, the last transmitted measurement packet has been lost
9
2 b
Flag PENDING_CONF. If 1, there is a pending configuration
change request.
9
9
9
9
3 b
If 1, there are more devices with the same Modbus address in
the network. The conflict must be solved.
9
4 b
If 1, there is a RF scheduling problem. The set transmission in-
terval is too short.
9
9
5
b
If 1, a network migration to another RF channel is in progress.
9
9
9
9
6
b
If 1, the device supports a rechargeable battery.
9
9
TAB. 11.3: Coils
– Read/Write parameters
Address Type
Coil description
AP ED RE AL
0 b
Waiting time after Modbus transmission:
0= immediate reception, 1=waiting time for 3.5 characters
9
1
b
Logging status: 0=active, 1=inactive
9
2
b
Logging mode: 0=non cyclic, 1=cyclic
9
3 b
Set 1 to delete the device logging memory. Bit zeroing is
automatic.
9
9
4 b
Buzzer activation (for AP and ED) or relays activation (for AL) in
case of measurement alarm: 0=no, 1=yes
9
9
9
5 b
If 1, there are unsaved device parameters in the flash mem-
ory. Set 0 to force storage.
9
6 b
If 1, there is a pending RF rescheduling (RF transmission se-
quence of devices). Set 0 to force rescheduling.
9
7 b
Flag CMD_FAILURE. If 1, at least a command sent to the de-
vice has failed. Set 0 to reinitialize the flag.
9
9
9
9
8
b
Buzzer activation in case of RF alarm: 0=no, 1=Yes
9
9 b
Protection of configuration with password: 0=no, 1=yes
Changing the parameter requires the Administrator password
(see Holding Register 10036).
9
13 b
Set 1 to reinitialize the counter in HD35EDH model with counter
input. Bit zeroing is automatic.
9
14 b
If 1, some device parameters in the base unit could be not up-
dated. Set 0 to force the update.
9
9
9
15 b
CO
2
sensor autocalibration: 0=OFF, 1=ON
9
16
b
Relay #1 activation in case of measurement alarm: 0=no, 1=yes
9
17
b
Relay #1 activation in case of RF alarm : 0=no, 1=yes
9
18
b
If 1, relay #1 is always active as long as the alarm persists
9
19
b
Relay #2 activation in case of measurement alarm: 0=no, 1=yes
9
20
b
Relay #2 activation in case of RF alarm : 0=no, 1=yes
9
21
b
If 1, relay #2 is always active as long as the alarm persists
9
TAB. 11.4: Input Registers
– Read-only parameters
Address Type
Input Register description
AP ED RE AL
Measured values and status of measurement alarms
0 SW
T
EMPERATURE
with
NTC10K
sensor of channel
1
in the set
measurement unit (x10).
9
1 B
Alarm for temperature with NTC10K sensor of channel 1:
0=OFF, 1= lower threshold alarm, 2= higher threshold alarm
9