 Installation and Operating Manual

IP227, Rev DA

Mobrey MCU200 Series 

February 2020

2.5

Extension cables

Extension cables up to 50 metres long can be fitted to most Mobrey ultrasonic sensors in the 
factory to special order, but a better site arrangement is to have a separate extension cable. 
When a double coaxial cable needs to be extended, two sets of coaxial plugs and sockets will be 
needed; one set for transmit, and one receive. Care must be taken that the connectors are not 
earthed, or shorted together in any way, to prevent cross-talk or pick-up. The coaxial 
connections must be made in a waterproof junction box. Terminal blocks should not be used. 
The extension cable needs to be of 50ohm characteristic impedance. Suitable dual coaxial 
extension cables can be purchased from Delta Mobrey (Part No. K178).

For extensions over 50 metres, it is recommended that two runs of single coaxial low-loss cable 
is used, with the transmit and return cable runs separated by 0.15 metres to minimise 
cross-talk. If several sensor cables are being run together then all the transmit cables (those 
connected to E2) should be grouped together and all receive cables (those connected to 1E) 
grouped together maintaining the separation specified above.

3.

Control unit installation

3.1

Safety matters

Review the safety information provided at the beginning of this user manual.

3.2

Mechanics

The control unit is supplied with three holes drilled in the bottom (longer) side of the box.
Two glands are supplied for the power input cable and relay output cable. The sensor is normally 
supplied fitted with a suitable gland on the cable. Two further holes can be drilled in the bottom 
side of the box should these be needed: it is recommended that the circuit board is removed 
whilst drilling extra gland holes.

Determine suitable mounting location with regards to:

Surface composition / load bearing capacity

Cable length restrictions

Accessibility for servicing

All cable connections are made to the terminal blocks along the bottom edge of the PCB (see 
fig.5). Release the terminal screw before inserting the wire.

Содержание Mobrey 402SD

Страница 1: ...anual IP227 Rev DA Mobrey MCU200 Series February 2020 Mobrey Ultrasonic Liquid Level Detection Systems for Interface Applications User Manual Control unit types MCU201 and MCU203 Ultrasonic gap sensor...

Страница 2: ...ctions must have a current rating of 25 A AC supply Never operate the equipment from a line voltage or frequency in excess of that specified Otherwise the insulation of internal components may break d...

Страница 3: ...is connected to its supply the opening of covers or removal of parts could expose live conductors The equipment must be disconnected from all power and signal sources before it is opened for any adjus...

Страница 4: ...MCU200 controller B Mobrey 402SD sensor C Mobrey 442SD sensor 2 Sensor installation 2 1 Safety matters Review all the safety information at the front of this manual 2 2 How ultrasonic gap sensors wor...

Страница 5: ...ther side of the gap In this orientation the switching level is half way up the sensor face If the sensor is mounted from the side of the tank the switching level is normally on the centreline of the...

Страница 6: ...cable runs separated by 0 15 metres to minimise cross talk If several sensor cables are being run together then all the transmit cables those connected to E2 should be grouped together and all receive...

Страница 7: ...ified A suitable switch or circuit breaker must be included in the installation and this should be in close proximity to the equipment and marked as its disconnecting device A suitable fuse rated at 3...

Страница 8: ...be used in all applications DPCO Double Pole Change Over relay connections There are two sets of contacts If the relay is connected to hazardous live mains circuits External circuits e g signal circu...

Страница 9: ...de switch is labelled FREQ and is located between the sensor terminal block E 2 and the Aux Input terminals This switch selects the operating frequency of the MCU200 oscillator which is either 3 7 MHz...

Страница 10: ...tory position is to the right for all switches OSC sensor oscillating E relay energised NE de energised Note Slide switches are adjustable using a pencil Ex factory settings are with all switches to t...

Страница 11: ...tch number 4 to the right E GREEN Figure 6 Example time delays for state changes A 2 seconds B 8 seconds C 30 seconds 4 Applications 4 1 Gain adjustment Correct adjustment of the gain is essential for...

Страница 12: ...nsor is normally suspended in the settling tank Similarly the control unit can be used with a Mobrey sludge pipe and a pair of 488S sensors to control the end of a de sludge cycle when thin solids are...

Страница 13: ...ercentage Settled sludge discharge control Reduce the timedelaysetting tomakeadjustments easier See RelayoutputandLEDlogic selection on page 10 for details Set the operating frequency on the control u...

Страница 14: ...Viscous liquids emulsions and liquids containing solid particles have a greater ultrasonic attenuation than clear liquids This technique is used to detect which liquid is present at the sensor e g th...

Страница 15: ...t is split at the interface into reflected and a refracted beams so that it does not reach the receiver crystal If there is no interference in the gap but only one liquid the beam is received and the...

Страница 16: ...can be then checked by linking the two terminals both labelled as E on the sensor terminals This should stop the Fault LED illuminating If the sensor is giving incorrect indications check the gain se...

Страница 17: ...by linking the sensor terminals 1 and 2 with a wire to simulate an oscillating sensor 7 Specifications 7 1 MCU201 Power supply 110 120 10 220 240 10 50 60 Hz Installation categories II IEC60664 for 23...

Страница 18: ...ensors are supported A switch on the PCB selects the electronics to operate at 1 MHz or 3 7 MHz Cable check option is supported for some sensors External input Available for keeping the relay de energ...

Страница 19: ...19 Installation and Operating Manual IP277 Rev DA Mobrey MCU200 Series February 2020...

Страница 20: ...y Limted Riverside Business Park Dogflud Way Farnham Surrey GU9 7SS 44 0 1252 729140 44 0 1252 729168 mobrey delta mobrey com Terms and Conditions of Sale are available upon request All other marks ar...

Отзывы: