Delta Elektronika SM 120-25 D Скачать руководство пользователя страница 8

SM3000

DELTA ELEKTRONIKA BV

1991, rev. May 2008

DESCRIPTIONS

Page 3 - 5

18)

IN SU LA TION

For safety the in su la tion of the sep a rat ing com po nents (trans-
formers) be tween in put and out put is tested at 3750 Vrms dur ing
1 min ute. This is tested be fore as sembling.

Warn ing!

 The 3750 Vrms can not be tested af terwards on the

as sem bled unit be cause the in su la tion be tween the com po -
nents on the in put side to the case (like the bridge rec tifier) is
spec i fied at 2500 Vrms. Since the in sulation out put - case is low
(only 600 V DC) the in sulation of the pri mary components to
case will break down when 3750 Vrms is ap plied be tween in put
and out put (2500 Vrms + 600 V DC < 3750 Vrms) (see also fig. 3
- 17).

Note:

 when testing the in sulation, take care to charge and dis -

charge the capacitors be tween in put - case and out put - case
slowly (e.g. in one sec ond). This to prevent high peak currents,
which could de stroy the power sup ply. Make sure to have dis -
charged the capacitors completely be fore us ing it again.

19)

RFI SUP PRES SION

Both the in put and out put have RFI fil ters, re sulting in very low
conducted RFI to the line and load. Due to the out put fil ter the
output voltage is very clean, hav ing al most no spikes.

20)

OP ER ATING TEMP

At full power the op erating tem perature range is –20 to +50 °C.
From 50 to 60 °C the output cur rent has to be de rated lin early to
75 % at 60 °C (see fig. 3 - 18). These tem peratures hold for nor -
mal use, i.e. the ven tilation open ings on the left and right side
must be free.

21)

THER MAL PRO TEC TION

A ther mal switch shuts down the out put in case of in sufficient
cooling. After cool ing down the unit will start work ing again.
The thermal pro tection circuit pro tects 2 parts sep arately in the
unit: the switching tran sistors on the pri mary side and the out put
cir cuit.
A trip ped ther mal pro tection can have the fol lowing ef fects:
1)  When the pro tection on the switching tran sistors has trip ped,
no led in dicator or digital me ter will burn on the front panel.
2)  When the pro tection on the output cir cuit has tripped, the
OVP led on the front panel will burn, and the OVP sta tus output
will be high.

22)

HOLD - UP TIME

The hold - up time de pends on the load, out put voltage and line
input voltage. A lighter load, a lower out put voltage or a higher
line in put voltage all re sult in a lon ger hold - up time (see fig.
3 - 19).

23)

TURN ON DE LAY

The out put voltage is avail able 0.5 sec after mains switch on.

24)

IN RUSH CUR RENT

The in rush current is limited by a 90 Ohm re sistor, re sulting in a
very low current dur 

ing switch on. The in 

put cur 

rent dur 

ing

switch on will be lower than dur ing op eration at full load.

25)

PHASE LOSS

Phase loss means that there is only one phase avail able in stead
of three.
The unit will con tinue to op erate on one phase but at 90% of the
max. out put volt age. Ex.: a SM30-100D on one phase 380 V can 
deliver 90% x 30 = 27 V @ 100 A. So if the output voltage is not
set higher than 27 V no drop in the output voltage will be noted
during phase loss. How ever the output rip ple volt age will be
slightly higher when the in put is on one phase.

fig. 3 - 16

Remote sensing on a pulsating load

fig. 3 - 17

In su la tion test voltages

fig. 3 - 18

Op er ating temper a ture ranges

fig. 3 - 19

Hold-up time vs Vout with Vin as a parameter

Содержание SM 120-25 D

Страница 1: ...5 200D SM 30 100D SM 45 70D SM 70 45D SM 120 25D SM 300 10D SM 3000 series Elso Philips Service Jilemnick ho 2 911 01 Tren n tel 421 32 6582410 7431690 fax 421 32 6582592 email elso elso sk web www el...

Страница 2: ...he protective earth terminal must be connected to the safety electrical ground before another connection is made Any interruption of the protective ground conductor or disconnection of the protective...

Страница 3: ...l Shock Instruction manual symbol The instrument will be marked with this symbol when it is necessary for the user to refer to the instruction manual Protective ground conductor terminal o Off supply...

Страница 4: ...r cuit 2 INPUT VOLTAGE The power supplies have a wide input volt age range The units need a 3 phase input voltage but no neutral connection is required The units can also operate on one phase but at 9...

Страница 5: ...lways use a shielded ca ble for programming The inputs have a protection circuit formed by a series resistor and a parallel zener see fig 3 7 The capacitor limits the speed to a safe value Note that t...

Страница 6: ...h 13 PROGRAMMING SPEED The response time is measured with a step waveform at the CV prog input Programming from a low to a high output voltage is nearly load independent but programming down to a low...

Страница 7: ...gh energy pulse of about 300 V If there is an electrical connection between the output and the input through the oscilloscope you will get a false reading The suppression for the SM120 25D is lower bu...

Страница 8: ...tch shuts down the output in case of insufficient cooling After cooling down the unit will start working again The thermal protection circuit protects 2 parts separately in the unit the switching tran...

Страница 9: ...ecommended for more than 3 units or in combination with Fast Programming option Consult factory for a solution 29 REMOTE SENSING The voltage at the load can be kept constant by remote sensing This fea...

Страница 10: ...re and full load the fan will run at a very low speed The fan does not operate on no load Normally at 50 C ambient and full load the fan will not work at full speed Since the fan is over rated it will...

Страница 11: ...TER circuit so no large inrush cur rent will flow As soon as the voltage is sufficiently high the power supply starts working and the series resistor is bypassed by a relay contact The operating switc...

Страница 12: ...recom mended to set the OVP on 24 3 27 V Check that the cooling of the unit is not obstructed 2 ANALOG PROGRAMMING Put the appropriate switch es in the position PROGRAM Connect the programming voltage...

Страница 13: ...put terminals so the OVP setting should be increased by the total voltage drop in the load leads 7 BATTERY CHARGER The CV CC regulated power supplies are ideal battery charg ers Once the output is set...

Страница 14: ...ecommended for more than 4 units consult factory for using more than 4 power supplies in parallel First connect output terminals and test system in normal paral lel operation Ensure that all power con...

Страница 15: ...PERATION For complex combinations as mixed series parallel always use the MASTER SLAVE SERIES ADAPTER product See fig 4 14 for an example of how to connect 2 units in se ries in parallel with 2 units...

Страница 16: ...supply to dry before switching it on again 3 GALVANIC INDUSTRY For using the power supplies in the galvanic industry it is strongly recommended to take precautions against an aggressive environ ment...

Страница 17: ...current is flowing through pin 1 of the prog connector Please check why current is flowing through pin 1 see also next paragraph 4 and fig 4 17 4 PROGRAMMING OFFSETS Unwanted offsets in the programmi...

Страница 18: ...not try to re pair P430 except for D400 D401 F400 and F401 but send P430 for repair or ask for replacement 10 CHECK POINTS IN CASE OF A SERIOUS FAILURE Check output diodes Defective diodes give a sho...

Страница 19: ...put with exactly 5 00 V Set output voltage to a low value en suring the power supply is in CC mode Measure the output current with an ac curate shunt Calibrate the current with R686 exactly on the rat...

Страница 20: ...l Journal of the European Communities EN 61204 3 EMC low voltage power supplies EN 61000 6 3 Generic Emissions residential light industrial EN 55022 Radiated and conducted Class B EN 61000 3 3 Voltage...

Отзывы: