Delta Elektronika SM 120-25 D Скачать руководство пользователя страница 17

DELTA ELEKTRONIKA BV

SM3000

Page 4 - 6

OPERATING  MAINTENANCE  TROUBLE SHOOTING  CALIBRATING

1991, rev. May 2008

TROUBLE SHOOTING

1)

GEN ERAL

In case you need as sistance for re pairing a unit, please con tact
our en gineers us ing the ad dress "

[email protected]

".

In case you want us to re pair the unit, please first fill out the
RMA-form be fore send ing the unit to us. Add ing a de tailed fault
description will help us to re pair the unit as soon as pos sible.
On our website

www.DeltaPowerSupplies.com

 the RMA-form

can be found un der 'Sup port'.

2)

NO OUT PUT (nor mal op er a tion)

Check in put fuses.

Check po si tion of prog. switches at the rear panel, they should be
on MAN UAL.

Check the connections on the SENSE BLOCK (at rear panel),
there should be a link be tween + and S+ and be tween – and S–.

Set OVP po tentiometer (at front panel) at maximum (fully clock
wise).

Switch on unit.

Turn both the CV and CC po tentiometer a few turns clock-wise. A
voltage should be pres ent on the output.

3)

PROGRAMMING DOES NOT WORK OK

Check po si tion of prog. switches at rear panel.

The unit works OK in manual con 

trol,

 but in pro gramming

mode the output voltage / cur rent has a large er ror.
Probably the fuse in se ries with Ø (pin 1) of prog. connector trip-
ped, the fuse (F600 = 650 mA) is a self-resetting type (see
fig. 4 - 16).

To check the fuse (F600) measure the voltage be tween Ø and the
minus out put, during the fault con dition. The volt age should only
be a few mV, a high volt age means that an un wanted cur rent is
flowing through pin 1 of the prog. con nec tor.
Please check why cur rent is flowing through pin 1 (see also next
para graph 4) and fig. 4 - 17).

4)

PRO GRAMMING OFF SETS

Unwanted off sets in the pro gramming can  be caused by
earth loops.

Fig ure 4 - 17 shows a typical earthing prob lem. In case the load
has a con nection to earth and the programming source as well,
problems could occur.  Improper choice of the earthing point of the
load can give a voltage drop of 

Δ

V1.  Con necting the mi nus or zero

to a sep arate earth con nection can give a volt age drop of 

Δ

V2. Be -

cause the in ternal wires of the pro gramming in put are thin, the
voltage drops

Δ

V1 and

Δ

V2 will be across the in ternal wir ing as

well. Re sulting in a error voltage in se ries with the pro gramming
volt age.

The best

so lu tion

 for this is us ing a float ing pro gramming source

with the help of the 

ISO AMP CARD

(

δ

-prod uct)

 or a floating load.

5)

STATUS OUTPUTS FAIL

Check fuse F601 in se ries with Ø (pin 8) (see fig. 4 - 16). To check
the fuse (F601) measure the resistance be tween Ø and the mi nus
output, an open circuit means a blown fuse. F601 = 650 mA.

6)

MASTER / SLAVE PAR ALLEL PROB LEMS

Ac ci den tal in ter rup tion of a mi nus lead of a unit dur ing op er a tion
will cause fuse F600 to blow (see fig. 4 - 16). To check the fuse
(F600) measure the resistance be tween Ø (pin 1 of prog. conn.)
and the mi nus out put, the fuse is a self re setting type.
F600 = 650 mA

Check link be tween pin 9 and 11 on the prog. con nector of the

slaves

Current sharing is not ok. Prob ably the links be tween S– and – of
the

 slaves

 are not re moved.

fig. 4 - 16

Lo ca tion of pro gram ming fuses on P432

P432 is situated on the rear panel

fig. 4 - 17

Un wanted pro gram ming off sets

Содержание SM 120-25 D

Страница 1: ...5 200D SM 30 100D SM 45 70D SM 70 45D SM 120 25D SM 300 10D SM 3000 series Elso Philips Service Jilemnick ho 2 911 01 Tren n tel 421 32 6582410 7431690 fax 421 32 6582592 email elso elso sk web www el...

Страница 2: ...he protective earth terminal must be connected to the safety electrical ground before another connection is made Any interruption of the protective ground conductor or disconnection of the protective...

Страница 3: ...l Shock Instruction manual symbol The instrument will be marked with this symbol when it is necessary for the user to refer to the instruction manual Protective ground conductor terminal o Off supply...

Страница 4: ...r cuit 2 INPUT VOLTAGE The power supplies have a wide input volt age range The units need a 3 phase input voltage but no neutral connection is required The units can also operate on one phase but at 9...

Страница 5: ...lways use a shielded ca ble for programming The inputs have a protection circuit formed by a series resistor and a parallel zener see fig 3 7 The capacitor limits the speed to a safe value Note that t...

Страница 6: ...h 13 PROGRAMMING SPEED The response time is measured with a step waveform at the CV prog input Programming from a low to a high output voltage is nearly load independent but programming down to a low...

Страница 7: ...gh energy pulse of about 300 V If there is an electrical connection between the output and the input through the oscilloscope you will get a false reading The suppression for the SM120 25D is lower bu...

Страница 8: ...tch shuts down the output in case of insufficient cooling After cooling down the unit will start working again The thermal protection circuit protects 2 parts separately in the unit the switching tran...

Страница 9: ...ecommended for more than 3 units or in combination with Fast Programming option Consult factory for a solution 29 REMOTE SENSING The voltage at the load can be kept constant by remote sensing This fea...

Страница 10: ...re and full load the fan will run at a very low speed The fan does not operate on no load Normally at 50 C ambient and full load the fan will not work at full speed Since the fan is over rated it will...

Страница 11: ...TER circuit so no large inrush cur rent will flow As soon as the voltage is sufficiently high the power supply starts working and the series resistor is bypassed by a relay contact The operating switc...

Страница 12: ...recom mended to set the OVP on 24 3 27 V Check that the cooling of the unit is not obstructed 2 ANALOG PROGRAMMING Put the appropriate switch es in the position PROGRAM Connect the programming voltage...

Страница 13: ...put terminals so the OVP setting should be increased by the total voltage drop in the load leads 7 BATTERY CHARGER The CV CC regulated power supplies are ideal battery charg ers Once the output is set...

Страница 14: ...ecommended for more than 4 units consult factory for using more than 4 power supplies in parallel First connect output terminals and test system in normal paral lel operation Ensure that all power con...

Страница 15: ...PERATION For complex combinations as mixed series parallel always use the MASTER SLAVE SERIES ADAPTER product See fig 4 14 for an example of how to connect 2 units in se ries in parallel with 2 units...

Страница 16: ...supply to dry before switching it on again 3 GALVANIC INDUSTRY For using the power supplies in the galvanic industry it is strongly recommended to take precautions against an aggressive environ ment...

Страница 17: ...current is flowing through pin 1 of the prog connector Please check why current is flowing through pin 1 see also next paragraph 4 and fig 4 17 4 PROGRAMMING OFFSETS Unwanted offsets in the programmi...

Страница 18: ...not try to re pair P430 except for D400 D401 F400 and F401 but send P430 for repair or ask for replacement 10 CHECK POINTS IN CASE OF A SERIOUS FAILURE Check output diodes Defective diodes give a sho...

Страница 19: ...put with exactly 5 00 V Set output voltage to a low value en suring the power supply is in CC mode Measure the output current with an ac curate shunt Calibrate the current with R686 exactly on the rat...

Страница 20: ...l Journal of the European Communities EN 61204 3 EMC low voltage power supplies EN 61000 6 3 Generic Emissions residential light industrial EN 55022 Radiated and conducted Class B EN 61000 3 3 Voltage...

Отзывы: