Delta Elektronika SM 120-25 D Скачать руководство пользователя страница 5

DELTA ELEKTRONIKA BV

SM3000

Page 3 - 2

DESCRIPTIONS

1991, rev. May 2008

3)

IN PUT CUR RENT

The in put cir cuit has a large se ries choke to im prove the waveform. The re -
sult is: a lower rms in put cur rent, less mains dis tortion and no large peak cur -
rents.
The units also have an in rush current limiter and a soft start circuit, for
smooth switch on.

°

FUSES  16 A Slow blow.

4)

STANDBY IN PUT POWER

The unit consumes very lit tle power when in standby. This makes it possible
to leave the in put power on and use the Re mote Shut Down in put (pin 5 on
prog. connector rear panel) to dis able the out put.

5)

EFFICIENCY

The ef ficiency is very high and constant over a wide output cur rent range
(see fig. 3 - 4). High efficiency also means low power loss and low heat gen -
er a tion.

6)

REG U LA TION

The load reg ulation should be measured di rectly on the out put terminals.
A few cm of ca ble can have a voltage drop of several mV (at high cur rent!).

7)

RIPPLE & NOISE

The out put rip ple is very low with al most no spikes.
The rip ple volt age has to be mea sured di rectly on the out put terminals us ing
a probe with very short con nections (to avoid pick up of mag netic fields) (see
fig. 3 - 5 and fig. 3 - 6).
At low tem per a tures like -20

°

C the rip ple in creases. By us ing high qual ity

elec tro lytic ca pac i tors the in crease is rel a tively low.

8)

PRO GRAMMING IN PUTS

The out put voltage and cur rent can be programmed by an ex ternal an alog
voltage. This pro 

gramming is very ac 

curate and lin 

ear, (non-lin 

ear ity

<0.15%). The levels are all standardized on 5V. Always use a 

shielded ca -

ble

 for pro gramming.

The in puts have a protection circuit formed by a series re sistor and a par allel
zener (see fig. 3 - 7). The ca pacitor limits the speed to a safe value. Note that
the an alog in puts (and outputs) are

not floating, but the common is con-

nected to the negative output terminal.

Wrong con nec tion of Ø can cause 

earth loops which can trip the fuse. After re moving the fault, the fuse will re -
set (PTC-fuse). To pre vent earth loops, use isolated pro gramming with the

ISO AMP CARD in ternal in terface op tion P145(

δ

-prod uct)

.

The pro gramming mode (program and man ual) can be se lected by means of 
the prog. switches which are sit uated be low the pro gramming con nector
(see fig. 3- 9).

9)

IEEE488 / RS232  PRO GRAMMING

For pro gram ming use the ex ter nal in ter face

PSC-488 mod ule

or in ter nal in-

ter face

PSC-232

(both

δ

-prod ucts)

.

Voltage and cur rent can easily be pro grammed and read back. Also the CC
and OVP sta tus can be read by the computer. Al ways use a 

shielded ca ble

for pro gram ming.

10)

MON I TORING OUT PUTS

The mon itor outputs give a voltage 0 - 5 V pro portional to the out put cur rent
or volt age. The output cur rent can easily be mea sured without an ex ternal
shunt us ing the I-monitor (see fig. 3 - 8). The mon itor outputs are buffered by
op-amp’s and protected by se ries re sistors and parallel zeners (see fig. 3 -
10). The ta ble 3 - 1 shows the impedance lev els of the mon itoring out puts.
For us ing Imon on a pul sating load, see paragraph 17) of this chapter.

fig. 3 - 4

Ef fi ciency  vs out put cur rent, SM30-100D

DC input , Vout = 30 V

fig. 3 - 5

Mea sur ing  rip ple volt age

WRONG !

fig. 3 - 6

Mea sur ing  rip ple volt age

RIGHT !

fig. 3 - 7

Pro gram ming in puts

(in ter nal cir cuit)

fig. 3 - 8

Ex ter nal  me ters

us ing  mon i tor out puts

Содержание SM 120-25 D

Страница 1: ...5 200D SM 30 100D SM 45 70D SM 70 45D SM 120 25D SM 300 10D SM 3000 series Elso Philips Service Jilemnick ho 2 911 01 Tren n tel 421 32 6582410 7431690 fax 421 32 6582592 email elso elso sk web www el...

Страница 2: ...he protective earth terminal must be connected to the safety electrical ground before another connection is made Any interruption of the protective ground conductor or disconnection of the protective...

Страница 3: ...l Shock Instruction manual symbol The instrument will be marked with this symbol when it is necessary for the user to refer to the instruction manual Protective ground conductor terminal o Off supply...

Страница 4: ...r cuit 2 INPUT VOLTAGE The power supplies have a wide input volt age range The units need a 3 phase input voltage but no neutral connection is required The units can also operate on one phase but at 9...

Страница 5: ...lways use a shielded ca ble for programming The inputs have a protection circuit formed by a series resistor and a parallel zener see fig 3 7 The capacitor limits the speed to a safe value Note that t...

Страница 6: ...h 13 PROGRAMMING SPEED The response time is measured with a step waveform at the CV prog input Programming from a low to a high output voltage is nearly load independent but programming down to a low...

Страница 7: ...gh energy pulse of about 300 V If there is an electrical connection between the output and the input through the oscilloscope you will get a false reading The suppression for the SM120 25D is lower bu...

Страница 8: ...tch shuts down the output in case of insufficient cooling After cooling down the unit will start working again The thermal protection circuit protects 2 parts separately in the unit the switching tran...

Страница 9: ...ecommended for more than 3 units or in combination with Fast Programming option Consult factory for a solution 29 REMOTE SENSING The voltage at the load can be kept constant by remote sensing This fea...

Страница 10: ...re and full load the fan will run at a very low speed The fan does not operate on no load Normally at 50 C ambient and full load the fan will not work at full speed Since the fan is over rated it will...

Страница 11: ...TER circuit so no large inrush cur rent will flow As soon as the voltage is sufficiently high the power supply starts working and the series resistor is bypassed by a relay contact The operating switc...

Страница 12: ...recom mended to set the OVP on 24 3 27 V Check that the cooling of the unit is not obstructed 2 ANALOG PROGRAMMING Put the appropriate switch es in the position PROGRAM Connect the programming voltage...

Страница 13: ...put terminals so the OVP setting should be increased by the total voltage drop in the load leads 7 BATTERY CHARGER The CV CC regulated power supplies are ideal battery charg ers Once the output is set...

Страница 14: ...ecommended for more than 4 units consult factory for using more than 4 power supplies in parallel First connect output terminals and test system in normal paral lel operation Ensure that all power con...

Страница 15: ...PERATION For complex combinations as mixed series parallel always use the MASTER SLAVE SERIES ADAPTER product See fig 4 14 for an example of how to connect 2 units in se ries in parallel with 2 units...

Страница 16: ...supply to dry before switching it on again 3 GALVANIC INDUSTRY For using the power supplies in the galvanic industry it is strongly recommended to take precautions against an aggressive environ ment...

Страница 17: ...current is flowing through pin 1 of the prog connector Please check why current is flowing through pin 1 see also next paragraph 4 and fig 4 17 4 PROGRAMMING OFFSETS Unwanted offsets in the programmi...

Страница 18: ...not try to re pair P430 except for D400 D401 F400 and F401 but send P430 for repair or ask for replacement 10 CHECK POINTS IN CASE OF A SERIOUS FAILURE Check output diodes Defective diodes give a sho...

Страница 19: ...put with exactly 5 00 V Set output voltage to a low value en suring the power supply is in CC mode Measure the output current with an ac curate shunt Calibrate the current with R686 exactly on the rat...

Страница 20: ...l Journal of the European Communities EN 61204 3 EMC low voltage power supplies EN 61000 6 3 Generic Emissions residential light industrial EN 55022 Radiated and conducted Class B EN 61000 3 3 Voltage...

Отзывы: