Configuration
Number of
processors
Heatsink
Processor/DIMM
blank
DIMM
blanks
Type of air
shroud
Fan
PowerEdge
R740xd with
mid bay
1
One 1U high performance
heat sink
Required
Required
Not required
Six high
performance
fans
PowerEdge
R740xd with
mid bay
2
Two 1U high performance
heat sink
Not required
Required
Not required
Six high
performance
fans
PowerEdge
R740xd with
GPU
2
Two 1U high performance
heat sink
Not required
Not
required
GPU air shroud
Six high
performance
fans
Ambient temperature limitations
The following table lists configurations that require ambient temperature less than 35°C.
NOTE:
The ambient temperature limit must be adhered to ensure proper cooling and to avoid excess CPU throttling, which may
impact system performance.
Table 31. Configuration based ambient temperature restrictions
System
Backplane
CPU Thermal
Design Power
(TDP)
CPU heat sink
Fan type
GPU
Ambient
restriction
PowerEdge
R740xd
12 x 3.5 inch SAS/
SATA + 4 x 2.5 inch
NVMe + 2 x 3.5
inch
70 W, 85 W, 105
W, 115 W, 125 W,
130 W, 140 W, 150
W, 165 W
1U high
performance
High performance
fan
N/A
30°C
12 x 3.5 inch SAS/
SATA + 4 x 2.5 inch
NVMe + 2 x 3.5
inch
150 W/8 core,
165 W/12 core,
200 W, 205 W
1U high
performance
High performance
fan
N/A
25°C
12 x 3.5 inch SAS/
SATA + 4 x 3.5 inch
+ 2 x 3.5 inch
150 W/8 core,
165 W/12 core,
200 W, 205 W
1U high
performance
High performance
fan
N/A
25°C
24 x 2.5 inch SAS/
SATA + 4 x 2.5 inch
+ 4 x 2.5 inch
150 W/8 core,
165 W/12 core,
200 W, 205 W
1U high
performance
High performance
fan
N/A
25°C
24 x 2.5 inch SAS/
SATA/NVMe with
adapter PERC
H740P
150 W/8 core,
165 W/12 core,
200 W, 205 W
1U high
performance
High performance
fan
≥1 double-width/
single-width
30°C
Particulate and gaseous contamination specifications
The following table defines the limitations that help avoid any equipment damage or failure from particulate and gaseous contamination. If
the levels of particulate or gaseous pollution exceed the specified limitations and result in equipment damage or failure, you may need to
rectify the environmental conditions. Remediation of environmental conditions is the responsibility of the customer.
Technical specifications
35
Содержание PowerEdge R740xd
Страница 9: ...Figure 1 Supported configurations PowerEdge R740xd system overview 9 ...
Страница 151: ...Figure 103 Installing GPU 2 and 3 Installing and removing system components 151 ...
Страница 208: ...Related link Removing the system cover Installing the system cover 208 Jumpers and connectors ...