242
Rack Mount Configuration
Connecting a Network Switch to a Rack PDU
CAUTION:
The PDU device’s A, B, and C power sockets are for network switches
only. Do not connect server enclosure(s) or server(s) to these sockets.
WARNING:
Exceeding 3 amps per outlet could cause sudden rack level power
loss.
Connect the network switch power cable to one of the three PDU AC power
sockets. See Figure 4-18.
Figure 4-18. Connecting the Network Switch Power Cable to the PDU
1
PDU device
2
AC power sockets (3)
3
network switch’s power cable
1
3
2