Installing System Components
197
a. In a 2+0 PSU configuration, a power sled blank or a C8220 compute sled must be installed in the
adjacent unoccupied bay to maintain proper cooling airflow in the enclosure.
Table 3-1. PSU and Power Sled Support Matrix
PSU
Config
Max.
Power
Redundant
Power
Sled
Shutdown
Maintenance Conditions
4+0
5600 W Not
supported
Required Shut down all sleds in the enclosure before
removing or replacing a power sled(s).
3+1
4200 W Supported Required Shut down all sleds in the enclosure before
removing or installing a power sled(s).
2+2
2800 W Supported Not
required
Power sleds can be removed or replaced
without powering off the sled(s) in the
enclosure.
2+1
2800 W Supported Required Shut down all sleds in the enclosure before
removing or replacing the power sled with
two PSU modules capacity.
2+0
a
2800 W Not
supported
Required Shut down all sleds in the enclosure before
removing or replacing a power sled(s).
1+1
1400 W Supported Not
required
Power sled can be removed or replaced
without powering off the sled in the
enclosure.
Содержание PowerEdge C8000
Страница 1: ...Dell PowerEdge C8000 Hardware Owner s Manual Regulatory Model B10S Regulatory Type B10S001 ...
Страница 41: ...About the System 41 Figure 1 24 Service Tag Location for C8000XD Storage Sled ...
Страница 160: ...160 Using the System Setup Program MIB Tree Diagram for FCB ...
Страница 170: ...170 Using the System Setup Program MIB Tree Diagram for PMC ...
Страница 185: ...Using the System Setup Program 185 ...
Страница 186: ...186 Using the System Setup Program ...
Страница 220: ...220 Installing System Components ...
Страница 250: ...250 Rack Mount Configuration ...
Страница 274: ...274 Troubleshooting ...
Страница 288: ...288 Jumpers and Connectors ...
Страница 290: ...290 Getting Help ...