Technical Specifications and Operating Limits
Operating Limits
The ambient temperature specification is measured at the front door
inlet. The site must have air conditioning of the correct size and
placement to maintain the specified ambient temperature range. The
air conditioning must be able to handle the BTU requirements of the
IP4700.
IMPORTANT:
The operating limits listed above for temperature and
humidity must not be exceeded inside the closed cabinet in which the IP4700
and any DAEs are mounted. Mounting equipment in a cabinet directly above
or below a IP4700 does not restrict air flow to the file server because air flows
through the IP4700 from front to back. Cabinet doors must not impede the
front to back air flow.
Requirement
Description
Ambient temperature
10
°
C to 40
°
C (50
°
F to 104
°
F)
Temperature gradient
10
°
C/hr (50
°
F/hr)
Relative humidity
20% to 80% noncondensing
Elevation
2438 m (8,000 ft) at 40
°
C; 3077 m (10,000 ft) at 37
°
C
Drive module power
25-W drive slot maximum (seeking)