Table 2 Hardware acclimation times (systems and components) (continued)
If the last 24 hours of the
TRANSIT/STORAGE
environment was this:
…and the OPERATING
environment is this:
…then let the system
or component
acclimate in the new
environment this many
hours:
Nominal 68-72°F
(20-22°C)
Nominal
40-55% RH
Nominal 68-72°F (20-22°C)
40-55% RH
0-1 hour
Cold <68°F
(20°C)
Dry <30%
RH
<86°F (30°C)
4 hours
Cold <68°F
(20°C)
Damp ≥30%
RH
<86°F (30°C)
4 hours
Hot >72°F
(22°C)
Dry <30%
RH
<86°F (30°C)
4 hours
Hot >72°F
(22°C)
Humid
30-45% RH
<86°F (30°C)
4 hours
Humid
45-60% RH
<86°F (30°C)
8 hours
Humid
≥60% RH
<86°F (30°C)
16 hours
Unknown
<86°F (30°C)
16 hours
NOTICE
l
If there are signs of condensation after the recommended acclimation time has
passed, allow an additional eight (8) hours to stabilize.
l
Systems and components must not experience changes in temperature and
humidity that are likely to cause condensation to form on or in that system or
component. Do not exceed the shipping and storage temperature gradient of
45°F/hr (25°C/hr).
Before You Begin
Hardware acclimation times
15
Содержание EMC VxFlex Ready Node 14G
Страница 1: ...Dell EMC VxFlex Ready Node 14G Hardware Installation Guide 302 004 321 REV 03 ...
Страница 6: ...FIGURES 6 Hardware Installation Guide ...
Страница 8: ...TABLES 8 Hardware Installation Guide ...
Страница 16: ...Before You Begin 16 Hardware Installation Guide ...
Страница 18: ...1U1N Procedures 18 Hardware Installation Guide ...
Страница 40: ...1U1N Configuration Equipment Installation 40 Hardware Installation Guide ...
Страница 48: ...Install AC Power Cables 48 Hardware Installation Guide ...
Страница 62: ...2U1N Procedures 62 Hardware Installation Guide ...
Страница 74: ...2U1N Configuration Equipment Installation 74 Hardware Installation Guide ...