4. Unigy II battery strings are typically supplied with connector package 1CU requiring one connector per post.
5. High rate applications will require multiple connectors to be used per cell post. A 2CU connector package will require 2 connectors per
connection (1 per side), see example below. A 4CU package will require 4 connectors per connection (2 per side) and a 6CU package
will require 6 connectors per connection (3 per side). Tighten & torque all bolts after all connectors are installed. Consult “Hardware
Torque Requirements” (pg b.4) for proper torque values.
b.9
1CU Package Detail
4CU Package Detail
6CU Package Detail
2CU Package Detail