b.10
6.
Some installations require a vertical “C” connector. This
“C” connector is limited to a 2CU connector package.
Consult below for proper installation for particular cell type
being installed.
5 to 7 Plate
Install spacer between cell post and “C” connector.
Duplicate connection process at both connection points.
Torque all hardware to 125 in-lb.
9 to 15 Plate
Install “C” connector to cell post.
Duplicate connection process at both connection points.
Torque all hardware to 125 in-lb.
17 to 27 Plate
1. Install “L” connector with vertical bolt as below. Bolt
should be installed loosely for future adjustments. Duplicate
connection process at both connection points
3. Ensure proper alignment of connectors to cell posts.
4.
Tighten & torque the horizontal bolt to 125 in-lb prior to
tightening and torqueing the vertical bolt in step 1.
NOTE: For this connection point it is acceptable to torque
the head of the bolt.
2. Install “C” connector to cell post using horizontal bolt
as below. Bolt should be installed loosely for future
adjustments. Duplicate connection process at both
connection points.