![Deka unigy II SPACESAVER Non-Interlock AVR 45 AH Скачать руководство пользователя страница 27](http://html.mh-extra.com/html/deka/unigy-ii-spacesaver-non-interlock-avr-45-ah/unigy-ii-spacesaver-non-interlock-avr-45-ah_installation-and-operation-manual_2465435027.webp)
b.27
Absorption
Float
Equalize
°C
Regulation Charge Maintenance °F
Charge
Charge
≥
35 2.370 2.220 2.400
≥
95
34
2.373
2.223
2.403
93.2
33
2.376
2.226
2.406
91.4
32
2.379
2.229
2.409
89.6
31
2.382
2.232
2.412
87.8
30
2.385
2.235
2.415
86.0
29
2.388
2.238
2.418
84.2
28
2.391
2.241
2.421
82.4
27
2.394
2.244
2.424
80.6
26
2.397
2.247
2.427
78.8
25
2.400
2.250
2.430
77.0
24
2.403
2.253
2.433
75.2
23
2.406
2.256
2.436
73.4
22
2.409
2.259
2.439
71.6
21
2.412
2.262
2.442
69.8
20
2.415
2.265
2.445
68.0
19
2.418
2.268
2.448
66.2
18
2.421
2.271
2.451
64.4
17
2.424
2.274
2.454
62.6
16
2.427
2.277
2.457
60.8
15
2.430
2.280
2.460
59.0
14
2.433
2.283
2.463
57.2
13
2.436
2.286
2.466
55.4
12
2.439
2.289
2.469
53.6
11
2.442
2.292
2.472
51.8
≤
10 2.445 2.295 2.475
≤
50
3mV per ºC
Renewable Energy (Cyclic)
Voltage Compensation
Renewable Energy (Cyclic)
Charge Parameters
Bulk Charge
Max. Current
Reference
(Amps)
Below Chart
Absorption (Regulation)Charge
Constant Voltage
2.35 - 2.40 vpc
Float Charge
Constant Voltage
2.24 - 2.26 vpc
Equalize Charger
Constant Voltage
2.40 - 2.43 vpc
Temperature Coefficient
3mV / °C
APPENDIX E