Output function
Auto
Test
Man
Block
Configurable
Output type
1
Status OK
X
X
X
X
Configurable
Constant
2
Run coil
X
X
X
X
Configurable
Constant
3
Stop coil
X
X
X
X
Configurable
Constant
4
Prepare
X
X
X
X
Configurable
Constant
5
Starter (Crank)
X
X
X
X
Configurable
Constant
6
Horn
X
X
X
X
Configurable
Constant
7
GB on
X
X
X
X
Configurable
Continuous
8
GB off
X
X
X
X
Configurable
Continuous
9
MB on (CGC 413 only)
X
X
X
X
Configurable
Continuous
10
MB off (CGC 413 only)
X
X
X
X
Configurable
Continuous
7.19.1 Functional description
1. Status OK
2. Run Coil
The relay configured to Run coil will be closed the entire time the engine is supposed to run.
3. Stop Coil
This relay will close to stop the engine, and when no running feedback is present, it will stay closed in the ext.
stop time (parameter 6212).
4. Prepare
This function will close the relay as the first thing in the start sequence. The relay will be closed for the time
programmed in parameter 6181. This function is used for preheating the engine or for prelubrication.
5. Starter (Crank)
The relay configured to starter will be closed for the time selected in parameter 6184 in the start sequence.
6. Horn
The horn relay is a common alarm output. This means that every time an alarm state appears, the horn relay
will close for the time configured in the parameter 6130 Alarm horn regardless of fail class. If 6130 is set to 0
seconds, it will be on until the reset horn push-button is activated or the alarm(s) has (have) been acknowl-
edged.
7. GB on
The function will close the generator breaker
8. GB off
This function will open the generator breaker
9. MB on (CGC 413 only)
This function will close the mains breaker
10. MB off (CGC 413 only)
This function vil open the mains breaker
CGC 400 DRH 4189340786 UK
Additional functions
DEIF A/S
Page 75 of 96