The alarm horn relay will activate
●
The alarm will be displayed in the alarm info screen
●
The generator breaker will open instantly
●
The genset is stopped instantly
●
The genset cannot be started from the unit (see next table)
The fail class "Trip MB/GB" will only trip the generator breaker if there is no mains breaker
present.
7.15.3 Engine stopped
Fail class
Action
Block engine start
Block MB sequence
Block GB sequence
1 Block
X
2 Warning
3 Trip GB
X
X
4 Trip + stop
X
X
5 Shutdown
X
X
6 Trip MB
X
7 Trip MB/GB
(X)
X
(X)
In addition to the actions defined by the fail classes, it is possible to activate one or two relay
outputs if additional relays are available in the unit.
The fail class "Trip MB/GB" will only block engine start and GB sequence if no mains breaker is
present.
7.15.4 Fail class configuration
The fail class can be selected for each alarm function either via the display or the PC software.
To change the fail class via the PC software, the alarm function to be configured must be selected. Select the
desired fail class in the fail class roll-down panel.
CGC 400 DRH 4189340786 UK