When the fuel pump is running, the fuel level must increase by 2% within the
fuel fill check
timer set in menu
6553. If the fuel level does not increase by 2% within the adjusted delay time, then the fuel pump relay deacti-
vates and a
Fuel fill alarm
occurs.
t
Fill check
∆ level, 2%
∆ level, 2%
The level of increase is fixed at 2% and cannot be changed.
7.15 Fail class
7.15.1 Fail class
All activated alarms must be configured with a fail class. The fail classes define the category of the alarms
and the subsequent alarm action.
Seven different fail classes can be used. The tables below illustrate the action of each fail class when the
engine is running or stopped.
7.15.2 Engine running
Fail class Action
Alarm horn
relay
Alarm dis-
play
Trip of gen.
breaker
Trip of
mains break-
er
Cooling-
down
genset
Stop
genset
1 Block
X
X
2 Warning
X
X
3 Trip GB
X
X
X
4 Trip + stop
X
X
X
X
X
5 Shutdown
X
X
X
X
6 Trip MB
X
X
X
7 Trip MB/GB
X
X
(X)
X
The table illustrates the action of the fail classes. If, for instance, an alarm has been configured with the "shut-
down" fail class, the following actions occur.
CGC 400 DRH 4189340786 UK
Additional functions
DEIF A/S
Page 67 of 96