Parame-
ter
Name
Function
6551
Fuel pump log.
start
Fuel transfer pump start point in percentage.
6552
Fuel pump log.
stop
Fuel transfer pump stopping point in percentage.
6553
Fuel fill check
Delay timer before activating fuel fill check alarm.
6554
Output A
The output relay to be used for control of the fuel pump. The selected relay
activates below the start limit and deactivates above the stop level.
6555
Type
The multi-input or external analogue input to be used for the fuel level sen-
sor.
Choose multi-input if 4-20 mA is used.
Choose "auto detection" if an RMI is used.
6556
Fail class
The fail class of the fuel fill alarm.
Setpoints available in menu 6550:
The fuel pump relay can be activated via M-Logic.
The output relay should be configured as a limit relay. Otherwise, an alarm will be raised when-
ever the output is activated.
The below drawing shows how the fuel pump is activated when the level reaches 20% and stopped again
when the level has reached 80%.
Fuel pump start level
Fuel level
80%
20%
Time
Fuel service tank level
Fuel pump stop level
7.14.1 Fuel fill check
The fuel pump logic includes a
Fuel fill check
function.
CGC 400 DRH 4189340786 UK