14
Remove soot from available space of combustion chamber, both on
the left and above the disassembled deflector.
The panel located on the right may be disassembled similarly. Dirt on
this side of the chamber is considerably smaller, so dismantling of this
side may not be necessary.
7.1.5.
EVERY YEAR SERVICE
It is recommended to clean the whole combustion chamber and flue
gas ducts once a year.
Cleaning of flue gas ducts:
1.
Remove the left front panel of the body.
2.
Remove the nuts from the cover of cleaning hole.
3.
Clean available flue gas ducts and cleaning hole.
7.1.6.
WINDOW PANEL CLEANING
It is recommended using a dry brush to clean the ceramic glass. If the
contamination is significant to use suitable cleaning agent spray and
spray little amount and then clean the window panel with a cloth.
Do not use abrasive products and do not spray the
product for window panel cleaning on painted parts and
gaskets of fireproof doors (cord made of ceramic fibre).
Do not open doors to clean the window panel during
operation of the fireplace. Cleaning of window panel is
possible only when the equipment is cold.
7.1.7.
DOORS/GASKETS
Abrasive surfaces of doors and closing mechanism should be occa-
sionally lubricated with graphite grease. Carry out inspection and clean-
ing of the whole stove prior to each heating season. Pay special atten-
tion to the condition of gaskets, replace them if necessary.
7.1.8.
FURNACE CHAMBER
Clean the furnace chamber of the stove periodically, depending on
moisture content and type of pellet used.
7.1.9.
FLUE
In compliance with applicable regulations, you should clean the flue two
times a year. The flue should be cleaned by a chimnysweep company
and this fact should be documented in this manual.
Flue gases coming out of blocked chimney are danger-
ous. Chimney and connector should be kept clean.
They should be cleaned before each heating season.
After a longer break in equipment’s operation, you
should check the flow capacity of the flue.
7.2.
PERIODIC INSPECTION BY AUTHORIZED SERVICE
After the heating season, it is necessary to clean several components
of the stove (combustion chamber, fan, container), including the com-
ponents where the flue gas flows through. This cleaning is obligatory
and is intended to remove all combustion residues. Because the in-
spection requires disassembly of the stove parts it should be carried
out only by qualified service.
Periodic inspection of the equipment should be car-
ried out only by a qualified manufacturer’s service.
7.3.
SHUTTING THE STOVE DOWN
It is recommended completely shutdown the stove and clean the equip-
ment when each heating season is finished.