CIRC. CURVE ...
Heating curve circuit A, B or C
x
Outside temperature (°C)
y
Water flow temperature (°C)
A
Maximum temperature of the circuit B - C
n
ANTICIP.A, ANTICIP.B, ANTICIP.C
A
Room temperature instruction - Comfort
Z
Room temperature instruction - Low
E
Time schedule
R
Anticipation time = Accelerated reheating phase
The anticipation function calculates the heating restart time to reach
the desired room temperature less 0.5 K at the time programmed for
switching to comfort mode.
The start time of the timed programmed corresponds to the end of the
accelerated reheating phase.
The function is activated by setting a different
OFF
value.
The value set corresponds to the time considered necessary to return
the installation to the required temperature (outside temperature
0°C), starting from a residual room temperature corresponding to the
low nocturnal instruction.
Anticipation is optimised if a room sensor is connected.
The regulator will automatically fine set the anticipation time.
This function is dependent on the surplus output available
in the installation.
n
SCREED DRYING
Used to force a constant flow temperature or a train to accelerate
screed drying on underfloor heating.
The setting for these temperatures must follow the screed-layer's
recommendations.
The activation of this parameter (setting other than
OFF
) forces the
permanent display of
SCREED DRYING
and deactivates all other
functions on the control unit.
When floor drying is active on a circuit, all other circuits (e.g. DHW)
are shut down. The use of this function is only possible on circuits B
and C.
M001678-B
1
0,5K
8801N033
1
4
2
3
MCA 25/28 BIC
5. Commissioning
15/06/12 - 300022159-001-01
73