8
Configuration C
93(x)
Air/flue gas connection by concentric pipes in the boiler
room and single pipes in the chimney (combustive air in
counter current in the chimney)
9
Configuration C
93(x)
Air/flue gas connection by concentric pipes in the boiler
room and single flex in the chimney (combustive air in
counter current in the chimney)
WARNING
4
Only factory components are authorised for
connecting the boiler and the terminal.
4
The clear section must comply with the
standard.
4
The chimney must be swept before the
installation of the evacuation conduit.
4.8.2.
Lengths of the air/flue gas pipes
For configurations B23 and C93, the lengths given in the
table are valid for horizontal conduits with a maximum
length of 1 metre. For each additional metre of horizontal
conduit, subtract 1.2 m from the vertical length Lmax
Type of air/flue gas connection
Diameter
Maximum length in
metres
MCA 25/28 BIC
B
33
Collective conduit
To determine the dimensions of such a system, refer to the supplier of the
collective conduit.
B
23
B
23P
Chimney (rigid or flexible duct in
chimney, combustive air taken from the
premises)
PPS
80 mm (Rigid duct)
40.0
80 mm (Flexible duct)
40.0
C
13(x)
Concentric pipes connected to a
horizontal terminal
Alu or PPS
60/100 mm
4.2
80/125 mm
20.0
C
33(x)
Concentric pipes connected to a vertical
terminal
Alu or PPS
60/100 mm
5.5
80/125 mm
20.0
C
43(x)
Collective conduit for sealed boiler (3
CEP)
To determine the size of such a system, consult the supplier of the 3 CEP
conduit.
C
53
Bi-flow adapter and separate single air/
flue gas ducts (combustive air taken
from outside)
Alu
60/100 mm
2 x 80 mm
40.0
C
83(x)
Collective conduit for sealed boiler
To determine the dimensions of such a system, refer to the supplier of the
collective conduit.
C
93(x)
Concentric pipes in the boiler room
Single conduits in the chimney
(combustive air in counter-current)
Alu or PPS
60/100 mm
60 mm (Rigid duct)
9.0
Concentric pipes in the boiler room
Flexible single conduit in the chimney
PPS
60/100 mm
80 mm (Flexible duct)
20.0
MCA 25/28 BIC
4. Installation
15/06/12 - 300022159-001-01
25