![DeDietrich Innovens MCA 25/28 BIC Скачать руководство пользователя страница 72](http://html1.mh-extra.com/html/dedietrich/innovens-mca-25-28-bic/innovens-mca-25-28-bic_installation-and-service-manual_2462465072.webp)
Installer level - Menu #SECONDARY INSTAL.P
Parameter
Adjustment range
Description
Factory
setting
Customer
setting
BUILD. INERTIA
(1)
0 (10 hours) to 10
(50 hours)
Characterisation of building's inertia:
0 for a building with low thermal inertia.
3 for a building with normal thermal
inertia.
10 for a building with high thermal inertia.
Modification of the factory setting is
only useful in exceptional cases.
3 (22 hours)
CIRC.CURVE A
(2)
0 to 4
Heating curve of the circuit A
¼
1.5
ANTICIP.A
(1)
0.0 to 10.0
Activation and adjustment of the
anticipation time
¼
NO
ROOM INFL. A
(1)
0 to 10
Influence of room sensor A
¼
3
CIRC.CURVE B
(2)
0 to 4
Heating curve of the circuit B
¼
0.7
ANTICIP.B
(1)
0.0 to 10.0
Activation and adjustment of the
anticipation time
¼
NO
ROOM INFL. B
(1)
0 to 10
Influence of room sensor B
¼
3
CIRC.CURVE C
(2)
0 to 4
Heating curve of the circuit C
¼
0.7
ANTICIP.C
(1)
0.0 to 10.0
Activation and adjustment of the
anticipation time
¼
NO
ROOM INFL. C
(1)
0 to 10
Influence of room sensor C
¼
3
SCREED DRYING
NO, B, C, B+C
Drying the floor
¼
NO
START DRYING TEMP
(3)
20 to 50 °C
Screed drying start temperature
20 °C
STOP DRYING TEMP
(3)
20 to 50 °C
Screed drying stop temperature
20 °C
NB DAYS DRYING
(3)
0 to 99
Number of days of floor drying
0
(1) The parameter is only displayed if
INSTALLATION
is set to
EXTENDED
(2) The parameter can be set to the heating curve by pressing key
f
(3) The parameter is only displayed if
SCREED DRYING
is other than
OFF
(4) The parameter is only displayed if
IN 0-10V
is set to
ON
.
(5) The parameter is only displayed if
P.DHW
is set to
PUMP
(6) If a reversal valve is connected, DHW priority will always be total regardless of the setting.
(7) The parameter is only displayed if
LEG PROTEC
is other than
OFF
5. Commissioning
MCA 25/28 BIC
70
15/06/12 - 300022159-001-01
Содержание Innovens MCA 25/28 BIC
Страница 7: ...15 06 12 300022159 001 01 5 ...
Страница 114: ...9 2 1 Casing EV 119526 1 1 T001498 B 1001 1002 1006 9 Spare parts MCA 25 28 BIC 112 15 06 12 300022159 001 01 ...
Страница 122: ...9 Spare parts MCA 25 28 BIC 120 15 06 12 300022159 001 01 ...
Страница 123: ......