![DeDietrich Innovens MCA 25/28 BIC Скачать руководство пользователя страница 106](http://html1.mh-extra.com/html/dedietrich/innovens-mca-25-28-bic/innovens-mca-25-28-bic_installation-and-service-manual_2462465106.webp)
Code Faults
Cause
of the
fault
Description
Checking / solution
D07
SYST.SENS.FAIL.
SCU
System sensor fault
Bad connection
4
Check whether the sensor is connected:
¼
See chapter: "Deletion of sensors from the
4
Check the link and the connectors
4
Check that the sensor has been correctly fitted
Sensor fault
4
Check the Ohmic value of the sensor
4
Replace the sensor if necessary
D09
DHW S.FAILURE
SCU
Domestic hot water sensor fault
Remarks:
Heating of domestic hot water
is no longer ensured.
The load pump operates.
The load temperature of the
dhw tank is the same as the
boiler.
Bad connection
4
Check whether the sensor is connected:
¼
See chapter: "Deletion of sensors from the
4
Check the link and the connectors
4
Check that the sensor has been correctly fitted
Sensor fault
4
Check the Ohmic value of the sensor
4
Replace the sensor if necessary
D11
D12
D13
ROOM S.A FAIL.
ROOM S.B FAIL.
ROOM S.C FAIL.
SCU
A room temperature sensor
fault
B room temperature sensor
fault
C room temperature sensor
fault
Note:
The circuit concerned operates
without any influence from the
room sensor.
Bad connection
4
Check whether the sensor is connected:
¼
See chapter: "Deletion of sensors from the
4
Check the link and the connectors
4
Check that the sensor has been correctly fitted
Sensor fault
4
Check the Ohmic value of the sensor
4
Replace the sensor if necessary
D14
MC COM.FAIL
SCU
Communication failure
between the SCU PCB and the
boiler radio module
Bad connection
4
Check the link and the connectors
Boiler module failure
4
Change the boiler module
D15
ST.TANK S.FAIL
SCU
Storage tank sensor fault
Note:
The hot water storage tank
reheating operation is no longer
assured.
Bad connection
4
Check whether the sensor is connected:
¼
See chapter: "Deletion of sensors from the
4
Check the link and the connectors
4
Check that the sensor has been correctly fitted
Sensor fault
4
Check the Ohmic value of the sensor
4
Replace the sensor if necessary
8. Troubleshooting
MCA 25/28 BIC
104
15/06/12 - 300022159-001-01
Содержание Innovens MCA 25/28 BIC
Страница 7: ...15 06 12 300022159 001 01 5 ...
Страница 114: ...9 2 1 Casing EV 119526 1 1 T001498 B 1001 1002 1006 9 Spare parts MCA 25 28 BIC 112 15 06 12 300022159 001 01 ...
Страница 122: ...9 Spare parts MCA 25 28 BIC 120 15 06 12 300022159 001 01 ...
Страница 123: ......