Tab.6
Cooling mode: outside air tempe35 °C, water temperature at the 18 °C. Performances in accordance
with EN 14511-2.
Measurement type
Unit
AWHP
4.5 MR
AWHP 6
MR-3
AWHP 8
MR-2
AWHP
11 MR-2
AWHP
11 TR-2
AWHP
16 MR-2
AWHP
16 TR-2
AWHP
22 TR–2
AWHP
27 TR–2
Cooling output
kW
3.80
4.69
7.90
11.16
11.16
14.46
14.46
17.65
22.20
Energy efficiency ratio
(EER)
4.28
4.09
3.99
4.68
4.68
4.43
4.43
3.80
3.80
Absorbed electrical
power
kWe
0.89
1.15
2.00
2.35
2.35
3.65
3.65
4.65
5.84
Tab.7
Common specifications
Measurement type
Unit
AWHP
4.5 MR
AWHP 6
MR-3
AWHP 8
MR-2
AWHP
11 MR-2
AWHP
11 TR-2
AWHP
16 MR-2
AWHP
16 TR-2
AWHP
22 TR–2
AWHP
27 TR–2
Total dynamic head at
nominal flow rate
kPa
62
61.80
49.30
39.30
39.30
21.30
21.30
—
—
Nominal air flow rate
m
3
/h
2680
2700
3000
6000
6000
6000
6000
8400
8400
Power voltage of the
outdoor unit
V
230
230
230
230
400
230
400
400
400
Start-up amperage
A
5
5
5
5
3
6
3
Maximal amperage
A
12
13
17
29.5
13
29.5
13
19
21
Acoustic power - In
side
dB(A) 43
43
51
51
51
51
51
43
43
Acoustic power - Out
dB(A) 58
65
65
69
69
69
69
77
77
Refrigerant fluid
R410A
kg
1.4
1.3
3.2
4.6
4.6
4.6
4.6
7.1
7.7
R410A refrigerant
tCO
2
e 2.922
2.714
6.680
9.603
9.603
9.603
9.603
14.821
16.074
Refrigerant connec
tion (Liquid - Gas)
inch
1/4 - 1/2 1/4 - 1/2 3/8 - 5/8 3/8 - 5/8 3/8 - 5/8 3/8 - 5/8 3/8 - 5/8 3/8 -
3/4
3/8 - 1
1/2 -
3/4
1/2 - 1
Max. pre-charged
length
m
7
10
10
10
10
10
10
20
20
(1) Noise radiated by the envelope - Test run in accordance with the NF EN 12102 standard, temperature conditions: air 7 °C, water 55 °C
(2) Noise radiated by the envelope - Test run in accordance with the NF EN 12102 standard, temperature conditions: air 7 °C, water 45 °C
for AWHP 4.5 MR only (inner and outer sides).
(3) Quantity of refrigerant calculated in tonnes of CO
2
equivalent
(4) Warning: the refrigerant connection lengths are limited to 20 m with the 3/4"gas pipe
Important
The quantity of refrigerant fluid in tonnes of CO
2
equivalent is
calculated using the following formula: quantity (in kg) of
refrigerant fluid x GWP / 1000. The Global Warming Potential
(GWP) of R410A is 2088.
3.3.2
Heat pump weight
Tab.8
Indoor module
Indoor mod
ule
Unit
MIT-S 4-8/E
MIT-S 4-8/H
MIT-S 11-16/E MIT-S 11-16/H MIT-S 22-27/E MIT-S 22-27/H
Net weight
kg
59
53
66
60
66
60
Gross weight kg
70
64
77
71
77
71
3 Technical specifications
7684505 - v03 - 14052020
MIT-S
13