Parameters
Description
Factory setting
Customer setting
AP016
Central heating operation:
0 = OFF
1 = ON
1
AP017
Domestic hot water tank operation:
0 = OFF
1 = ON
1
AP073
SUMMER / WINTER set point switch:
Can be set from 15 to 30 °C.
Set to 30.5 °C = function deactivated
22°C
AP074
SUMMER override:
0 = OFF
1 = ON
0
CP040
Post-operation time of the generator pump
Can be set from 0 to 20 minutes
4 minutes
CP071
Room temperature set point in reduced mode
Can be set from 5 to 30°C.
16°C
CP072
Room temperature set point in comfort mode
Can be set from 5 to 30°C.
20°C
CP073
Not available on this version
CP074
Not available on this version
CP075
Not available on this version
CP076
Not available on this version
CP140
Set point cooling activity zone 1
Can be set from 20 to 30°C.
30°C
CP141
Set point cooling activity zone 2
Can be set from 20 to 30°C.
25°C
CP142
Set point cooling activity zone 3
Can be set from 20 to 30 °C.
25 °C
CP143
Set point cooling activity zone 4
Can be set from 20 to 30°C.
25 °C
CP144
Set point cooling activity zone 5
Can be set from 20 to 30 °C.
25 °C
CP145
Set point cooling activity zone 6
Can be set from 20 to 30 °C.
25 °C
CP320
Circuit operating mode:
0 = Timer program
1 = Manual
2 = Frost protection
0
CP570
Not available on this version
DP020
Post-circulation time of the reversal valve after domestic hot
water production:
Can be set from 0 to 99 minutes
Set to 99 = continuous running
3 minutes
DP060
Number of timer programs selected for domestic hot water
production mode
Can be set from 0 to 2
0
DP070
Domestic hot water temperature set point in comfort mode
Can be set from 40 to 80 °C.
54 °C
DP080
Domestic hot water temperature set point in reduced mode
Can be set from 10 to 60°C.
10°C
DP200
Domestic hot water production mode:
0 = Program
1 = Manual
2 = Frost protection mode
0
6 Settings
7623755 - v02 - 03072015
MIV-4
35