2. Select the AP015 cooling parameter by pressing the or key
and confirm by pressing the
key.
3. Select cooling function shut-down by pressing the key and con
firm by pressing the
key.
4. Go back to the main display by pressing the
h
key.
5.4 Frost Protection
If the temperature of the heating water in the heat pump falls too much,
the integrated protection device switches itself on. This device functions as
follows:
If the water temperature is lower than 5°C, the circulating pump starts
up.
If the water temperature is lower than 3°C, the back-up starts up.
If the water temperature is higher than 10°C, the back-up shuts down
and the circulating pump continues to run for a short time.
The radiator valves in rooms where there is a risk of frost must be fully
open.
Fig.34 Cooling function
MW-6000365-1