3 Technical specifications
3.1 Homologations
3.1.1 Directives
This product complies with the requirements of the following European Di
rectives and Standards:
Low Voltage Directive 2006/95/EC
Generic standard: IEC/EN 60335–1
Relevant Standard: IEC/EN 60335–2–40
Electromagnetic Compatibility Directive 2004/108/EC
Generic standards: IEC/EN 61000-6-3, IEC/EN 61000-6-1
Relevant Standard: IEC/EN 55014
This product conforms to the requirements of European Directive
2009/125/EC on the ecodesign of energy-related products.
In addition to the legal requirements and guidelines, the supplementary
guidelines in this manual must also be followed. Supplements or subse
quent regulations and guidelines that are valid at the time of installation
shall apply to all regulations and guidelines specified in this manual.
3.2 Technical data
3.2.1 Heat pump
Maximum operating pressure: 0.3 MPa (3 bar)
Tab.3
Conditions of use
Water (°C)
Outside air (°C)
Limit operating temperatures in heating
mode
+18 / +60
AWHP 4 MR, AWHP 6 MR-2 : -15 / +35
Other models: -20 / +35
Limit operating temperatures in cooling
mode
+7 / +25
+7 / +40
Tab.4
Heating mode: outside air tempe7°C, water temperature at the 35°C. Performances in accordance with
EN 14511-2.
Measure
ment type
Unit
AWHP 4
MR
AWHP 6
MR-2
AWHP 8
MR-2
AWHP 11
MR-2
AWHP 11
TR-2
AWHP 16
MR-2
AWHP 16
TR-2
Heat output kW
3.94
5.73
8.26
11.39
11.39
14.65
14.65
Coefficient
of perform
ance (COP)
4.53
4.04
4.27
4.65
4.65
4.22
4.22
Absorbed
electrical
power
kWe
0.87
1.42
1.93
2.45
2.45
3.47
3.47
Nominal
amperage
A
4.11
6.57
8.99
11.41
3.8
16.17
5.39
Nominal wa
ter flow rate
(ΔT = 5K)
m
3
/hour
0.68
0.99
1.42
1.96
1.96
2.53
2.53
Tab.5
Heating mode: outside air tempe2°C, water temperature at the 35°C. Performances in accordance with
EN 14511-2.
Measure
ment type
Unit
AWHP 4
MR
AWHP 6
MR-2
AWHP 8
MR-2
AWHP 11
MR-2
AWHP 11
TR-2
AWHP 16
MR-2
AWHP 16
TR-2
Heat output kW
3.76
3.19
5.30
10.19
10.19
12.90
12.90
3 Technical specifications
16
MIV-4
7623755 - v02 - 03072015