4
14
Function
Code
Name
Setting Range
Factory
Setting
Description
Setting time from zero to max
Acceleration
b05.03
0.1~3600s
Model
The setting time from max. frequency
to zero
Deceleration
Time
b05.04
0.1~3600s
Model
Set
Time
Set
Frequency
Determine the Acc./Dec. rate
Maximum
Output
Frequency
b05.05
10-600Hz
50Hz
Maximum running frequency
Up limit of
Output
Frequency
b05.06
b05.07~
b05.05
(Maximum
Frequency)
50Hz
The minimum running frequency of
pump
Lower limit of
Output
Frequency
b05.07
0Hz~b05.07 20Hz
Use to check the noise of motor and
controller ’s interference to the
surroundings. A high carrier makes a
low motor noise, but leads to a big
temperature rise and interference.
Should not be altered if unnecessary.
Carrier
Frequency
b05.08
1~15kHz
Model
Set
Low Pressure
(LP) Restart
Delay Time
b05.09
0~60min
10min
In case of low pressure, b05.09=0,
the controller restarts according to
the setting time automatically, without
artificial restart. b05.09=0, restart
invalid
Alternating
Time
b05.10
0~300h
8h
In order to balance and prolong the
pump service life to set the parameter,
unit: hour. When the parameter is set
to 0.0, it means no alteration.
Operational time of master and
auxiliary pump switches over
according to the setting alternating
time