4
12
Function
Code
Name
Setting Range
Factory
Setting
Description
Transducer fault detecting setting
value, corresponding to full range
(100%), when the detecting time
exceeds feedback lost time, it is
d e e m e d a s m a l f u n c t i o n b y
transducer, the system will report
E022 as transducer fault code.
b02.08
0.0~100.0% 1.0%
Al1 Feedback
Lost Detecting
Value
b02.09
0.0~100%
0.0%
AI2 Feedback
Lost Detecting
Value
b02.10
0.0~3600s
1.0s
Feedback Lost
Detecting Time
00: Master Controller
01~05: Auxiliary Controller
06~31: Reserved
Communication
Address
b03.00
0~31
02
Data of master and slave comes
into the rate
0: 1200BPS 1: 2400BPS
2: 4800BPS 3: 9600BPS
4: 19200BPS 5: 38400BPS
Band Rate
Selection
b03.01
0~5
3
Data Format (parity check)
Data Format
b03.02
0~5
0
Interval of data responding
Communication
Delay Time
b03.03
0~200ms
15ms
If the interval time exceeds the setting
value, the system will report E018 as
fault
Communication
Timeout Delay
0.0: invalid
b03.04
0~100s
0.0s
0: Halt and display alarm
1: Do not display alarm, continue
Communication
Error Action
b03.05
0~1
0
0: Responding to write operation
1: Un-responding to writer operation
Communication
Response
Action
b03.06
0~1
0
E n s u r e t h e e f f e c t s o f d a t a
transmission, long-time setting will
slow down data transmission and
short-time setting will easily make
mistakes
Data
Transmission
Time Interval
b03.07
0.05~2.00s
0.10s