b04.03
Wake up
pressure
bias
Determines how low the pressure
falls before pump restarts during
sleep mode e.g. if setting (L)=3.0
bar, bias b04.03=0.5bar, the pump
will restart again when pressure falls
to 3.0-0.5=2.5bar.
0-20 bar 0.5bar
0.5bar
b04.04
Sleeping
Bias
The pressure fluctuation that allows
sleeping. If pressure rises by this set
value b04.04 for time b04.01, it
enters sleep mode.
0-1bar
0bar
0.5bar
23
b05.00
Water
level
control
Water level switch connection style;
0: Invalid 1: NC 2: NO
0-2
2
1
Code
Setting
Range
Name
Description
Factory
Setting
Recommend
-ed Setting
b03.00
Commun
ication
Address
00: Master Controller
01-05: Auxiliary controller (slaves)
06-31: Reserved
Auxiliaries should be set as 01-on
0N on order assuming N auxiliary
controllers
0-31
2
00-0N
b03.08
Slave
Quantity
0: None
Slave number, assume 1 master N
slaves, set as N
0-5
0
N
b03.09
Fault
Shift/
Standby
master
Fault Master Shift.
I f i n v a l i d , S e t 2 .
If valid, Set Master as 0 and Slave 1
as 1; slave 1 to act as standby
master
W i t h Fa u l t s h i f t , c o n n e c t a
redundant transducer to the slave 1.
No need to modify other slaves.
0-2
2
0-1
b04.00
Sleeping
function
0: Invalid 1: Valid
Automatically Stop when there is no
water consumption
0-1
1
1
b04.01
Sleeping
time
Delay time in seconds
0-300s
5s
10s