3
3.3.3 ID-NET™
C-BOX 100/150 Pin Name
Function
38
ID-NET+
High speed internal
36
ID-NET-
High speed internal network-
39 GND
ground
The following instructions are referred to Figure 23, Figure 24 and Figure 25:
•
Use DeviceNet cables (drop type 2 x AWG 24 + 2 x AWG 22).
•
Cable Shield connected only to Master earth.
•
Max 1000 meter ID-NETcable length.
•
Connect only 36, 38 and not 39 (use only 2 wires).
•
DC Voltage Power cable (VS – GND) should be handled as a signal cable (i.e.
do not put it together with AC cable):
-
Wire dimensioning must be checked in order to avoid voltage drop greater
than 0.8 Volt.
-
Cable should lie down as near as possible to the ID-NET cable (avoiding
wide loop between them).
•
Scanner's chassis may be connected to earth.
•
Network inside the same building.