AMT58x-PB Profibus® 

14 

5 - Quick reference 

5.1 Configuring the encoder via Siemens STEP7 

5.1.1 Importing GSD file 

Profibus encoders are supplied with their own GSD file 

AMT58-xxx-

 

13x12-PB

 (see the enclosed documentation, if supplied, or click

 

D

atalogic

 website

). 

WARNING 
Install the AMT58_Vx.GSx in the AMT58 series multiturn encoders 
GSD installation file is further available in both Italian (.GSI) and 
English (.GSE) versions (texts and comments are in the supported 
language). 

WARNING 
For AMT58 multiturn encoders the default value preset by Datalogic 
in the Counts per revolution item of the 

AMT58-xxx-13x12-PB

 GSD 

file is 4096 (12 bits); for this reason, if you have a 25-bit multiturn 
encoder and you want to use the overall resolution, you must set the 
Counts per revolution item to 8192 (13 bits). See EXAMPLE 2 on 
page 20. 

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

Содержание AMT58-PB Series

Страница 1: ...Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...

Страница 2: ... Datalogic logo are registered trademarks of Datalogic S p A in many countries including the U S A and the E U All brand and product names mentioned herein are for identification purposes only and may be trademarks or registered trademarks of their respective owners Datalogic shall not be liable for technical or editorial errors or omissions contained herein nor for incidental or consequential dam...

Страница 3: ...stic LEDs Figure 1 13 5 Quick reference 14 5 1 Configuring the encoder via Siemens STEP7 14 5 1 1 Importing GSD file 14 5 1 2 Adding a node to the project 16 5 1 3 Encoder configuration parameters 17 5 2 Reading the diagnostic information 25 5 3 Setting the Preset value 27 6 Profibus interface 28 6 1 GSD file 28 6 2 Classes of the Device profile 29 6 3 Operating modes 29 6 4 DDLM_Set_Prm 31 6 4 1 ...

Страница 4: ...Subject index Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...

Страница 5: ...t where information of great significance for the user can be found user must pay the greatest attention to them Instructions must be followed strictly in order to guarantee the safety of the user and a correct use of the device Failure to heed a warning or comply with instructions could lead to personal injury and or damage to the unit or other equipment This icon followed by the word NOTE is mea...

Страница 6: ... the first section general information concerning the safety the mechanical installation and the electrical connection as well as tips for setting up and running properly and efficiently the unit are provided In the second section entitled Profibus Interface both general and specific information is given on the Profibus interface In this section the interface features and the parameters implemente...

Страница 7: ...re connecting the device connect according to explanation in section 4 Electrical connections in compliance with the 2004 108 EC norm on electromagnetic compatibility following precautions must be taken before handling and installing discharge electrical charge from your body and tools which may come in touch with the device power supply must be stabilized without noise install EMC filters on devi...

Страница 8: ... by manufacturer unit with solid shaft in order to guarantee the maximum reliability over time of the mechanical parts we recommend a flexible coupling to be installed to connect the encoder and the installation shaft make sure the misalignment tolerances of the flexible coupling are respected unit with hollow shaft the encoder can be mounted directly on a shaft whose diameter has to respect the t...

Страница 9: ... is listed in the delivery document too Please always quote the ordering code and the serial number when reaching Datalogic Automation s r l for purchasing spare parts or needing assistance For any information on the technical characteristics of the product refer to the technical catalogue Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...

Страница 10: ...he encoder shaft fix the encoder to the flange 2 or to the mounting bell by means of screws 3 secure the flange 2 to the support or the mounting bell to the motor mount the flexible coupling 1 on the motor shaft make sure the misalignment tolerances of the flexible coupling 1 are respected 3 1 1 Customary installation a mm b mm c mm d mm AMT58 36 H7 48 3 1 2 Installation using fixing clamps option...

Страница 11: ...AMT58x PB Profibus 5 3 1 3 Installation using a flange code ST 58 FLNG Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...

Страница 12: ...sing the reducing sleeve 8 if supplied Avoid forcing the encoder shaft fasten the fixing plate 4 to the rear of the motor using two M3 cylindrical head screws 5 fix the collar 3 to the encoder shaft apply threadlocker to screw 3 Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...

Страница 13: ...rmination resistance are located inside the encoder connection cap Thus you must remove the connection cap to access any of them NOTE Be careful not to damage the internal components when you perform this operation To remove the connection cap loosen the two screws 1 Please be careful with the internal connector Always replace the connection cap at the end of the operation Take care in re connecti...

Страница 14: ...ee Figure use 1 TCEI M3 x 6 cylindrical head screw with 2 tooth lock washers 4 3 Connection cap with PGs Figure 1 Figure 1 Connection cap is fitted with three PG9 cable glands for bus IN bus OUT connections as well as power supply connection The bus cables can be connected directly to the terminal connectors located in front of each cable gland We recommend Profibus DP certificated cables to be us...

Страница 15: ...connector A coding frontal side male Pin Function 1 10VDC 30VDC 3 0 VDC GND 4 1 Shield Case 1 Shield is also connected to pin 4 to allow the connection of the shield even if the plug connector has a plastic case Profibus signals M12 connector B coding frontal side male BUS IN female BUS OUT Pin Function 1 n c 2 Profibus A Green 3 n c 4 Profibus B Red 5 n c Case Shield n c not connected Buy www Val...

Страница 16: ...s operation The node address must be set via hardware using the DIP A dip switches located inside the connection cap Allowed addresses are from 0 to 125 The default value is 1 The node address must be entered also in the software interface please refer to section 5 1 2 Adding a node to the project on page 16 Turn the power supply off and set the node number in binary value consider that ON 1 OFF 0...

Страница 17: ...ware during the configuration of the node Slave This device supports the following baud rates they are listed in the GSD file too 9 6 kbit s 19 2 kbit s 93 75 kbit s 187 5 kbit s 500 kbit s 1 5 Mbit s 3 Mbit s 6 Mbit s 12 Mbit s The following table shows the maximum transmission rates in relation to permissible line length Baud rate Kbit s 9 6 19 2 93 75 187 5 500 1500 12000 Max cable length 1200 ...

Страница 18: ...ion on the last device in the transmission line Use the RT Switch to activate or deactivate the bus termination RT Description 1 2 ON Activated if the encoder is the last device in the transmission line 1 2 OFF Deactivated if the encoder is not the last device in the transmission line Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...

Страница 19: ... not recognized OFF ON Correct function communication is on the device is sending receiving messages OFF Flashing The encoder is operating within the limits of the Red Zone for any information see section 6 8 Red zone ON Flashing Configuration parameters are not valid ON OFF Transmission time out error Flashing ON Bus communication failure Flashing Flashing Flash memory error unrestorable error Bu...

Страница 20: ...ion file is further available in both Italian GSI and English GSE versions texts and comments are in the supported language WARNING For AMT58 multiturn encoders the default value preset by Datalogic in the Counts per revolution item of the AMT58 xxx 13x12 PB GSD file is 4096 12 bits for this reason if you have a 25 bit multiturn encoder and you want to use the overall resolution you must set the C...

Страница 21: ...e window that appears you can select the GSD file specific to the unit you need to install in your Siemens control system Choose among the available files the one you need GSD file for AMT58 multiturn encoder in either Italian or English language Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...

Страница 22: ...T58 Class 2 submodule In this way you set the class of the device for further details on available classes see section 6 2 Classes of the Device profile on page 29 After having installed the node by double clicking on the graphic icon of the unit you have just installed you enter the page designed to configure the bus properties In this page you can both enter the node address configured via hardw...

Страница 23: ...then right click the item and press the Object Properties command in the shortcut menu The Properties DP slave window will appear In the Parameter Assignment page all configuration data parameters available for the device are listed For a comprehensive description of the parameters and how to set them properly refer to the specific explanation in section 6 4 DDLM_Set_Prm on page 31 Class 1 example...

Страница 24: ...llowing examples to understand how the Total resolution value has to be divided into two parts a high part and a low part WARNING You can set new values next to the Counts per revolution and Total resolution items only if Class 2 functionality ENABLED if Scaling function ENABLED the set resolution values are enabled and used by the encoder on the contrary if Scaling function DISABLED you are allow...

Страница 25: ...its 4096 4096 16777216 We want to set 4096 counts per revolution and 4096 revolutions Thus we will set 4096 next to the Counts per revolution item The Total resolution value will be 4096 cpr 4096 rev 1677721610 0x1000000 The value to be set in the Total resolution items will be as follows Total resolution high Total resolution low Value 0100 0000 hexadecimal 256 0 decimal Buy www ValinOnline com P...

Страница 26: ...n the Total resolution items will be as follows Total resolution high Total resolution low Value 0200 0000 hexadecimal 512 0 decimal WARNING When you set a new value next to the Counts per revolution item please always check also the Total resolution items value and be sure that the resulting number of revolution complies with the Hardware number of revolutions of the device The same when you set ...

Страница 27: ...e encoder is required to carry out more than 93000 revolutions this cannot be as the hardware number of revolutions is as stated 4096 When this happens the encoder falls into an error signalling the faulty condition through the diagnostic LEDs see on page 13 You are allowed to set any integer value less than or equal to the Hardware counts per revolution in the Counts per revolution item while you...

Страница 28: ...r revolution item The Total resolution value will be 2048 cpr 1024 rev 209715210 0x200000 The value to be set in the Total resolution items will be as follows Total resolution high Total resolution low Value 0020 0000 hexadecimal 32 0 decimal WARNING We recommend the Number of revolutions to be set to a value that is a power of 2 If the set number of revolutions is not a power of 2 the so called R...

Страница 29: ... 4096 16777216 We want to set 4096 counts per revolution and 50 revolutions 50 is NOT a power of 2 Thus we will set 4096 next to the Counts per revolution item The Total resolution value will be 4096 cpr 50 rev 20480010 0x32000 The value to be set in the Total resolution items will be as follows Total resolution high Total resolution low Value 0003 2000 hexadecimal 3 8192 decimal Buy www ValinOnli...

Страница 30: ... we will set 360 next to the Counts per revolution item The Total resolution value will be 360 cpr 4000 rev 144000010 0x15F900 The value to be set in the Total resolution items will be as follows Total resolution high Total resolution low Value 0015 F900 hexadecimal 21 63744 decimal After having set new parameter values click the OK button to close the Properties DP Slave window and then the Downl...

Страница 31: ... it is necessary to connect to the unit i e enter the online status To do this select Station Open online in the HW Config window or click the Online Offline button see the icon on the left When the unit is online select the AMT58 module first and then the PLC Module Information command to enter the Module Information window Finally open the DP Slave Diagnostics page Click the Hex Format button to...

Страница 32: ...AMT58x PB Profibus 26 6 byte diagnostics Byte Description 0 status 1 1 status 2 2 status 3 3 Master ID 4 manufacturer ID 5 Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...

Страница 33: ...example in the paragraph Preset on page 38 Finally click the Command variables button in the Toolbar see the right icon Now the position of the encoder is 0000 0500hex To close the Preset procedure set the bit 31 of the variable AD 100 back to 0 and then click the Command variables button again NOTE It may occur that some data variables having index higher than 127 or data greater than 4 bytes are...

Страница 34: ...tall the AMT58 xxx 13x12 PB GSx in the AMT58 series multiturn encoders Vx is intended to indicate the GSD file version GSD installation file is further available in both Italian AMT58 xxx 13x12 PB GSI and English AMT58 xxx 13x12 PB GSE versions texts and comments are in the supported language WARNING For AMT58 multiturn encoders the default value preset by Datalogic in the Counts per revolution it...

Страница 35: ... parameter Class 2 allows to use all Class 1 functions and further extended functions they are scaling function see the Scaling function parameter 6 3 Operating modes Profibus DP devices allow operation using different communication modes see Figure below NOTE All parameters are transmitted when the Set_Prm mode is active with the exception of the Preset value Preset value is transmitted only when...

Страница 36: ...It sets the number of bytes used for data transmission in Data_Exchange mode see section 6 5 DDLM_Chk_Cfg on page 37 DDLM_Data_Exchange This is the standard operation mode It is used either by the Master to send the Preset value and by the Slave to transmit the Position value see the section 6 6 DDLM_Data_Exchange on page 38 DDLM_Slave_Diag It is used when the power is turned on and whenever the M...

Страница 37: ...es according to the working specifications you want to set Data transmission is carried out according to the specifications of the encoder profile as shown in the following tables DDLM_Set_Prm Byte Parameter 0 9 Reserved for PROFIBUS network 10 Operating parameters bit 0 Code sequence bit 1 Class 2 functionality bit 2 Reserved bit 3 Scaling function Bits 4 7 Reserved 11 12 Counts per revolution 13...

Страница 38: ...t 1 Enabled Encoder Class 2 is set Default 1 min 0 max 1 Scaling function When this option is disabled Scaling function 0 the device uses the hardware resolution i e the hardware counts per revolution and the hardware number of revolutions see the encoder data on the label applied to the device when the option is enabled Scaling function 1 the device uses the resolution set in the bytes 11 16 Coun...

Страница 39: ...counts per revolution However we suggest setting a value that is a power of 2 1 2 4 2048 4096 Default 4096 min 1 max 8192 for AMT58 multiturn encoder WARNING If you set a value greater than the maximum allowed value i e greater than the Hardware counts per revolution value the encoder falls into an error signalling the faulty condition through the diagnostic LEDs see on page 13 WARNING When you se...

Страница 40: ...he number of distinguishable steps over the total measuring range The total resolution of the encoder results from the product of Counts per revolution by Number of revolutions Byte 13 14 15 16 Bit 31 24 23 16 15 8 7 0 Data 231 to 224 223 to 216 215 to 28 27 to 20 You are allowed to set any integer value less than or equal to the Hardware total resolution However we suggest setting a value that is...

Страница 41: ...on page 41 WARNING The AMT58 multiturn encoder can be configured so that it works exactly as the singleturn encoder This is achieved by setting Total resolution Counts per revolution Let s suppose the encoder is set as follows Counts per revolution 8192 Total resolution 8192 So it follows that Number of revolutions 8192 Total resolution 1 8192 Counts per revolution This is exactly the configuratio...

Страница 42: ...s are set next to the Counts per revolution and or Total resolution items also a new Preset value is required It has to comply with the new resolution you have set WARNING Please note that the in Step 7 the Total resolution value has to be split into two separate fields namely Total resolution high and Total resolution low This value in fact must be entered in two words Please refer to the example...

Страница 43: ...r of bytes used for the Data_Exchange as viewed from the Master side Chk_Cfg message structure 1 byte bit 7 Consistency 1 bit 6 Word format 0 byte 1 word 4 bytes bits 5 4 In out data 01 Input 10 Output bits 3 0 Length code Example bit 7 6 5 4 3 2 1 0 Dat a 1 1 0 1 0 0 0 1 D1h 1 1 1 0 0 0 0 1 E1h D1hex 4 byte input E1hex 4 byte output Buy www ValinOnline com Phone 844 385 3099 Email CustomerService...

Страница 44: ...e previous and following positions will get a value according to it This function is useful for example when the zero position of the encoder and the zero position of the axis need to match The preset value will be set for the position of the encoder in the moment when the preset value is sent The Preset value is sent by the Master to the Slave in Data_Exchange mode by setting bit 31 1 for 3 cycle...

Страница 45: ...ex 0000000 02 0000000 02 0010001 02 0110011 12 2 M S 80 00 05 00 S M 00 00 22 67 3 M S 80 00 05 00 S M 00 00 05 00 WARNING Always set the Preset value when the encoder shaft is in stop The new Preset value is saved immediately after receipt Please refer also to the example for setting the preset value via Step7 refer to the section 5 3 Setting the Preset value on page 27 Buy www ValinOnline com Ph...

Страница 46: ...logic encoders implement the standard diagnostic information 6 bytes For any information on the DP Slave diagnostics please refer to the Profibus Specification document 6 byte Diagnostic Byte Description 0 status 1 1 status 2 2 status 3 3 Master ID 4 manufacturer ID 5 Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...

Страница 47: ... set Total resolution value When the encoder crosses the limit of the last Total resolution section thus entering the red zone a counting error occurs i e a jump in the position count The problem can be represented graphically in the Figure below Example 25 bit resolution multiturn encoder Hardware counts per revolution 8192 213 Hardware number of revolutions 4096 212 Hardware total resolution 335...

Страница 48: ...000 cpr 96 revolutions 480000 counts 9519999 9999999 the transmitted position is consistent with the set resolution it is calculated so that the last position within the red zone before crossing the zero position is Total resolution 1 Please be careful using the position information sent by the encoder when it is operating within the limits of the red zone When the encoder crosses from the normal ...

Страница 49: ...SD file for AMT58 multiturn encoder AMT58 xxx 13x12 PB GSx Lista parametri Valore di default Code sequence 0 Class 2 functionality 1 Scaling function 1 Counts per revolution 8196 Total resolution 33554432 Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...

Страница 50: ...Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...

Страница 51: ...tomation S r l Datalogic and the Datalogic logo are registered trademarks di Datalogic S p A in many countries including the U S A and the E U Tutti i marchi e i nomi di prodotti qui citati servono al solo scopo di identificazione e possono essere marchi o marchi registrati dei propri rispettivi proprietari Datalogic non risponde di eventuali errori tecnici o tipografici o di omissioni qui contenu...

Страница 52: ...he project 14 5 1 3 Encoder configuration parameters 14 5 2 Reading diagnostic information 16 5 3 Setting the Preset value 18 5 4 Set node number via BUS 19 6 Profibus interface 20 6 1 GSD file 20 6 2 Classes of the Device profile 20 6 3 Modes of operation 21 6 4 DDLM_Set_Prm 22 6 4 1 Byte 10 Operating parameters 23 Code sequence 23 Class 2 functionality 24 Scaling function control 24 Diagnostic t...

Страница 53: ...volution 25 D Diagnostic type 24 E Exchange type 24 P Position and velocity values 29 Position value 28 Preset value 29 S Scaling function control 24 T Total resolution 26 V Velocity measure unit 28 Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...

Страница 54: ...t where information of great significance for the user can be found user must pay the greatest attention to them Instructions must be followed strictly in order to guarantee the safety of the user and a correct use of the device Failure to heed a warning or comply with instructions could lead to personal injury and or damage to the unit or other equipment This icon followed by the word NOTE is mea...

Страница 55: ... the first section general information concerning the safety the mechanical installation and the electrical connection as well as tips for setting up and running properly and efficiently the unit are provided In the second section entitled Profibus Interface both general and specific information is given on the Profibus interface In this section the interface features and the parameters implemente...

Страница 56: ...re connecting the device connect according to explanation in section 4 electrical connections in compliance with the 2004 108 EC norm on electromagnetic compatibility following precautions must be taken before handling and installing discharge electrical charge from your body and tools which may come in touch with the device power supply must be stabilized without noise install EMC filters on devi...

Страница 57: ...characteristics declared by manufacturer unit with solid shaft in order to guarantee maximum reliability over time of mechanical parts we recommend a flexible coupling to be installed to connect the encoder and user s shaft make sure the misalignment tolerances of the flexible coupling are respected unit with hollow shaft the encoder can be mounted directly on a shaft whose diameter has to respect...

Страница 58: ...isted in the delivery document too Please always quote the ordering code and the serial number when reaching contatta Datalogic Automation s r l for purchasing spare parts or needing assistance For any information on the technical characteristics of the product refer to the technical catalogue Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...

Страница 59: ...der to the flange 2 or to the mounting bell by means of screws 3 secure the flange 2 to the support or the mounting bell to the motor mount the flexible coupling 1 on the motor shaft make sure the misalignment tolerances of the flexible coupling 1 are respected 3 1 1 Customary installation a mm b mm c mm d mm AMT58 36 H7 48 3 1 2 Fissaggio con graffe codice ST 58 KIT a mm b mm c mm d mm AMT58 36 H...

Страница 60: ...AMT58x PB Profibus 5 3 1 3 Installation using a flange code ST 58 FLNG Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...

Страница 61: ...sing the reducing sleeve 8 if supplied Avoid forcing the encoder shaft fasten the fixing plate 4 to the rear of the motor using two M3 cylindrical head screws 5 fix the collar 3 to the encoder shaft apply threadlocker to screw 3 Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...

Страница 62: ... Thus you must remove the connection cap to access any of them NOTE Be careful not to damage the internal components when you perform this operation To remove the connection cap loosen the two screws 1 Please be careful with the internal connector Always replace the connection cap at the end of the operation Take care in re connecting the internal connector Tighten the screws 1 using a tightening ...

Страница 63: ...h 2 tooth lock washers 4 3 Connection cap with PG gland BC PB connection cap is fitted with three PG9 cable glands for bus IN and bus OUT connections and power supply connection The bus cables can be connected directly to the terminal connectors located in front of each cable gland We recommend Profibus DP certificated cables to be used Core diameter should not exceed Ø 1 5 mm 0 06 inches Terminal...

Страница 64: ...nector A coding frontal side male Pin Function 1 10VDC 30VDC 3 0 VDC GND 4 1 Shield Case 1 Shield is also connected to pin 4 to allow the connection of the shield even if the plug connector has a plastic case Profibus signals M12 connector B coding frontal side male BUS IN female BUS OUT Pin Function 1 n c 2 Profibus A Green 3 n c 4 Profibus B Red 5 n c Case Shield n c not connected Buy www ValinO...

Страница 65: ...p This has to be activated as line termination in the last device Use RT Switch to activate or deactivate the bus termination RT Description 1 2 ON Activated if the encoder is the last device in the transmission line 1 2 OFF Deactivated if the encoder is not the last device in the transmission line 4 7 Baud rate The baud rate is set by the Master via software during configuration of the node slave...

Страница 66: ... power supply off and set the node number in binary value consider that ON 1 OFF 0 bit 1 LSB 2 3 4 5 6 7 MSB 8 not used 20 21 22 23 24 25 26 Example Set node number 25 2510 0001 10012 binary value bit 1 2 3 4 5 6 7 8 20 21 22 23 24 25 26 ON OFF OFF ON ON OFF OFF OFF Set node number 55 5510 0011 01112 binary value bit 1 2 3 4 5 6 7 8 20 21 22 23 24 25 26 ON ON ON OFF ON ON OFF OFF Buy www ValinOnli...

Страница 67: ...d Power green Event OFF OFF No power supply or hardware fault OFF ON Correct operation correct communication OFF Flashing Red Zone see section 6 9 Red Zone ON Flashing Configuration parameters not valid ON OFF Transmission time out error Flashing ON Bus communication failure Flashing Flashing Flash memory error Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...

Страница 68: ...h their own GSD file AMT58 xxx 16x14 FBUS PB see enclosed documentation or Datalogic website In the menu bar of the HW Config window press Options and then Install New GSD command Select the correct GSD file in the installation window and install it Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...

Страница 69: ...to the variables table in the bottom right in this way you set the class of the device for further details see section 6 2 Classes of the Device profile 5 1 3 Encoder configuration parameters To enter the Encoder configuration parameters window select the device in the bottom right of the HW Config window and right click to open the menu then choose the Object Properties command Buy www ValinOnlin...

Страница 70: ...tting each parameter refer to section 6 4 DDLM_Set_Prm Class 2 example Class 2 VEL example After having set new parameter values click the OK button to close the Properties DP slave window and then the Download button see icon on the left in the toolbar of the HW Config window to download set parameters Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...

Страница 71: ...sary to connect to the unit enter online status To do this select Station Open online in the HW Config window or click the Online Offline button see icon on the left Then select PLC Module information to enter the Module information window Finally open the DP Slave Diagnostic page Click the Hex Format button to display diagnostic information Buy www ValinOnline com Phone 844 385 3099 Email Custome...

Страница 72: ...e suggest setting the 16 byte diagnostic If diagnostic information is not used it is recommended to set 16 byte diagnostic see 5 1 3 Encoders configuration parameters section See section 6 7 DDLM_Slave_Diag for a complete list and meaning of each diagnostic byte Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...

Страница 73: ...lue is loaded into variables ED 104 107 4 bytes The Preset value is sent to the encoder using variables AD 100 103 4 bytes The current position of the encoder is 0003 7AA1hex To set the Preset value 0000 0500hex set bit 31 of variable AD 100 1 8000 0500hex Finally click Command variables button in the Toolbar see right icon Now the position of the encoder is 0000 0500hex Buy www ValinOnline com Ph...

Страница 74: ...sed 5 4 Set node number via BUS To access this function PLC must be able to run the SAP55 service To set the node number via BUS set dip switches to address 126 0111 11102 DIP A To set node number select PLC PROFIBUS Assign PROFIBUS Address in the SIMATIC Manager window and open the Assign PROFIBUS Address window Choose the current address 126 in the first Current PROFIBUS Address combo box and th...

Страница 75: ...s must be set when configuring the device Class 1 allows basic functions of the device and should be used for sending the position value see parameter Position value changing the counting direction see parameter Code sequence setting the preset value see parameter Preset value Class 2 allows to use Class 1 functions and extended functions such as scaling function see Scaling function control diagn...

Страница 76: ...ction 6 4 DDLM_Set_Prm DDLM_Chk_Cfg Sets the number of bytes used for data transmission in Data_Exchange mode see section 6 5 DDLM_Chk_Cfg DDLM_Data_Exchange Used as standard operation mode Used by Master to send the Preset value used by Slave to transmit position and velocity values see section 6 6 DDLM_Data_Exchange DDLM_Slave_Diag Used when power is turned on and whenever Master needs to know d...

Страница 77: ...et Data transmission is carried out in compliance with values set for the encoder profile and shown in the following tables DDLM_Set_Prm with Class 1 Byte Parameter 0 9 Reserved for PROFIBUS network 10 Operating parameters bit 0 Code sequence bit 1 Class 2 functionality bits2 5 Reserved bit 6 Diagnostic type bit 7 Exchange type 11 20 Reserved DDLM_Set_Prm with Class 2 Byte Parameter 0 9 Reserved f...

Страница 78: ...tionality disabled enabled 2 Reserved 3 Scaling function control disabled enabled 4 5 Reserved 6 Diagnostic type reduced large 7 Exchange type pos pos vel Code sequence It defines whether the position value output by the transducer increases when the encoder shaft rotates clockwise CW or counterclockwise CCW When Code sequence 0 the position value increases when the encoder shaft rotates clockwise...

Страница 79: ... new values next to the Counts per revolution and Total resolution items only if Class 2 functionality ENABLED if Scaling function control ENABLED the set resolution values are enabled and used by the encoder on the contrary if Scaling function control DISABLED you are allowed to set new resolution values however they are not enabled even if sent to the encoder the encoder still goes on using the ...

Страница 80: ...8 27 to 20 Allowed values are equal to or lower than Hardware counts per revolution value We suggest setting power of 2 values 1 2 4 2048 4096 Setting a value greater than allowed causes the resolution to be forced to Hardware counts per revolution value Default 262144 min 1 max 262144 for HS58 Default 65536 min 1 max 65536 for HM58 WARNING When you set a new value next to Counts per revolution it...

Страница 81: ...ng function control See the section 6 4 1 Byte 10 Operating parameters on page 23 This parameter is intended to set the number of distinguishable steps over the total measuring range The total resolution of the encoder results from the product of Counts per revolution by Number of revolutions Byte 15 16 17 18 Bit 31 24 23 16 15 8 7 0 Data 231 to 224 223 to 216 215 to 28 27 to 20 Allowed values are...

Страница 82: ...turn 218 262144 cpr Hardware number of turns 1 Total hardware resolution 18 bit 262144 1 262144 HM5816 16384 FB xx multiturn encoder Hardware counts per revolution 16 bit turn 216 65536 cpr Hardware number of turns 14 bit 16384 turn Total hardware resolution 30 bit 65536 16384 230 1073741824 Example Multiturn encoder HM5816 16384 FB 6 with BC PB C connection cap Resolution is Hardware counts per r...

Страница 83: ...cture 1 byte bit 7 Consistency 1 bit 6 Word format 0 byte 1 word 4byte bit 5 4 In out data 01 Input 10 output bit 3 0 Length code Example bit 7 6 5 4 3 2 1 0 Dat a 1 1 0 1 0 0 0 1 D1h 1 1 0 1 0 0 1 1 D3h 1 1 1 0 0 0 0 1 E1h Class 1 and Class 2 D1hex 4 byte input E1hex 4 byte output Class 2 VEL D3hex 8 byte input E1hex 4 byte output 6 6 DDLM_Data_Exchange This is the normal operation status of the ...

Страница 84: ...osition of the axis need to match The preset value will be set for the position of the encoder in the moment when the preset value is sent The Preset value value is sent by the Master to the Slave in Data_Exchange mode by setting bit 31 1 for 3 cycles The MSB of the preset value controls the preset function in the following way Normal operating mode MSB 0 bit 31 the encoder will make no change in ...

Страница 85: ...it 31 24 23 16 15 8 7 0 1 M S 80 00 10 00 S M 00 05 50 00 2 M S 80 00 10 00 S M 00 05 50 00 3 M S 80 00 10 00 S M 00 00 10 00 NOTE We suggest setting the Preset value when the shaft is in stop The new Preset value is saved immediately after receipt Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...

Страница 86: ...g DDLM_Set_Prm operating parameters byte 10 see section 6 4 1 Byte 10 Operating parameters 16 byte Diagnostic Byte Description Byte Description 0 Status 1 8 Operating status 1 Status 2 9 Encoder type 2 Status 3 10 Hardware single turn resolution 3 Master ID 11 4 Manufacturer ID 12 5 13 6 Extended diagnostic header 14 Hardware number of revolution 15 7 Alarms 63 byte Diagnostic Buy www ValinOnline ...

Страница 87: ...oder type 41 10 Hardware single turn resolution 42 11 43 Programmed total resolution 12 44 13 45 14 Hardware number of revolution 46 15 47 Serial number 16 Additional alarms 48 17 Supported alarms 49 18 50 19 Warnings 51 20 52 21 Supported warnings 53 22 54 23 Profile version 55 24 56 25 Software version 57 Reserved 26 58 Reserved 27 Operating time 59 Reserved 28 60 Reserved 29 61 Reserved 30 62 R...

Страница 88: ... must be able to run the SAP55 service Set dip switch to address 126 0111 11102 DIP A The message has the following DATA bytes Byte Description 0 New node number 1 Manufacturer ID 2 3 Lock node number 0 not supported Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...

Страница 89: ...e To calculate it we must subtract the Total resolution value from the Hardware total resolution of the device as many times as until the difference is less than the the set Total resolution value When the encoder crosses the limit of the last Total resolution section thus entering the red zone a counting error occurs i e a jump in the position count The problem can be represented graphically in t...

Страница 90: ...ll work within the Red Zone limits NOTE The Red Zone status is indicated by the green LED flashing while the red LED is OFF see the section 4 9 Diagnostic LEDs on page 12 Within the limits of the Red Zone the transmitted position is coherent with setting resolution it is calculated so that the last position transmitted before zero position is Total resolution 1 Make attention using the values sent...

Страница 91: ...sequence 0 Class 2 functionality 1 Scaling function control 1 Diagnostic type 0 Exchange type Class 1 and Class 2 0 Class 2 VEL 1 Counts per revolution 16384 Total resolution 1073741824 Velocity measure unit 0 Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...

Отзывы: