DK-40 USER MANUAL V2.6 (02.08.2011)
K13D01-E - 28 -
No
Description
Adjustment Range
Factory set
P55
High Frequency Alarm
Value
60.0 ... 990.0 Hz
62.0 Hz
P56
Frequency display
0
: Disable
1
: Enable
1
P57
Phase L1 voltage display
0
:Disable
1
:Enable
0
P58
Phase L2 voltage display
0
:Disable
1
:Enable
0
P59
Phase L3 voltage display
0
:Disable
1
:Enable
0
P60
Phase L1-L2 voltage display
0
:Disable
1
:Enable
1
P61
Phase L2-L3 voltage display
0
:Disable
1
:Enable
1
P62
Phase L3-L1 voltage display
0
:Disable
1
:Enable
1
P63
MODBUS enable
0
: Disable
1
: Enable
1
P64
Master/Slave MODBUS
0
: Slave
1
: Master
0
P65
MODBUS node address
1
: Starts multiple controller opr.
2 ... 254
: Modbus address
240
P66
Slave Start Timer (Multiple
controller operation)
1..999 sec.
180 sec
P67
Master Change Period
(Multiple operation)
1..999 hours
100 hours
P68
Serial Number Low Word
0 ... 65535
10
P69
Serial Number High Word
0 ... 65535
10
P70
High Voltage Alarm Enable
0
: Disable
1
: Enable
If this parameter is set to
0
, the
P71 parameter will not be
displayed.
1
P71
High Voltage Alarm Limit
200 ... 650 V
445
P72
Phase Order Check Enable
0
: Disable
1
: Enable
1