DK-40 USER MANUAL V2.6 (02.08.2011)
K13D01-E - 30 -
No
Description
Adjustment Range
Factory set
P83
Pressure sensor-2 low
pressure alarm limit (if
adjusted to 0.0 then no
alarm is given)
0.. (P79-0.5)
0
P84
Reserved
-
0
P85
Reserved
-
0
P86
Reserved
-
0
P87
Reserved
-
0
P88
Service security selection
0:
Service request gives warning
only
1:
Service request stops the
compressor as explained in
chapter_5.
0
P88
Reserved
-
0
P89
Variable Hour counting
method
0
: Fixed hour counting coefficient
1
: Variable hour counting method
Refer chapter 6.3 for more
details.
0
P90
Pressure Dot Display
0
: Enable
1
: Disable
If this parameter is set to
0
, the
pressure is displayed in xx.x
format. This format is useful for
display in
bars
.
If this parameter is set to
1
, the
pressure is displayed in xxx
format. This format is useful for
display in
psi
.
0