DK-40 USER MANUAL V2.6 (02.08.2011)
K13D01-E - 22 -
8. RELAY OUTPUTS
The unit provides 5 relay outputs. 4 of them have fixed function, while RL5 has
selectable function.
Relays with fixed function:
RL1
= LINE relay
RL2
= DELTA relay
RL3
= STAR relay
RL4
= LOAD relay
RL5
can be programmed for below functions through parameter
P40
:
RELAY FUNCTION
DESCRIPTION
0
ALARM
RL5 operates if alarm exists, releases otherwise.
1
FAN
If the air end temperature equals or greater than P41, then
RL5 is on. If the air end temperature is lower than
(P41-P42), then RL5 is off.
2
LOAD
RL5 = RL4
3
NO LOAD
RL5 = opposite of RL4
4
MOTOR RUNNING RL5 operates if the main motor runs, releases otherwise.
5
MOTOR STOPPED
RL5 operates if the main motor is stopped, releases
otherwise.
6
FLA
Ş
ÖR RÖLE
Released during timer P41
Active during timer P42 .