DK-40 USER MANUAL V2.6 (02.08.2011)
K13D01-E - 35 -
10.2. MODBUS REGISTER LIST
CONTROLLER REGISTERS
ADDR. NAME
DESCRIPTION
LENG.
R/W
TYPE
MUL.
40001 Frequency
16 BIT
R-O
unsigned word
0.1
40002 Phase L1 Voltage
16 BIT
R-O
unsigned word
1
40003 Phase L2 Voltage
16 BIT
R-O
unsigned word
1
40004 Phase L3 Voltage
16 BIT
R-O
unsigned word
1
40005 Phase L1-L2 Voltage
16 BIT
R-O
unsigned word
1
40006 Phase L2-L3 Voltage
16 BIT
R-O
unsigned word
1
40007 Phase L3-L1 Voltage
16 BIT
R-O
unsigned word
1
40008 Pressure
Pressure Value
16 BIT
R-O
unsigned word
0.1
40009 Air end temperature
Temperature Value
16 BIT
R-O
signed word
1
40010 Motor PTC ohm
read in ohms
16 BIT
R-O
signed word
1
40011 Temperature 2
Measured from Sensor 2
16 BIT
R-O
signed word
1
40012 Pressure 2
Measured from Sensor 2
16 BIT
R-O
unsigned word
0.1
40013
Service A Counter
remaining time to service A
32 BIT
R-O
signed long
0.1
40014
40015
Service B Counter
remaining time to service B
32 BIT
R-O
signed long
0.1
40016
40017
Service C Counter
remaining time to service C
32 BIT
R-O
signed long
0.1
40018
40019
Service D Counter
remaining time to service D
32 BIT
R-O
signed long
0.1
40020
40021
Service E Counter
remaining time to service E
32 BIT
R-O
signed long
0.1
40022
40023
Total Working Hour
Total controller time
(LOAD + STOP)
32 BIT
R-O
unsigned long
0.1
40024
40025
Total Engine Hour
Total Engine working
hour(LOAD+UNLOAD)
32 BIT
R-O
unsigned long
0.1
40026
40027
Total Load Hour
Total Engine loaded
hour(LOAD)
32 BIT
R-O
unsigned long
0.1
40028
40029
Alarms
alarm bits (see alarm list at
chapter 10.3)
32 BIT
R-O
unsigned long
1
40030
40031 Warnings
warnings bits (see alarm list
at chapter 10.3)
16 BIT
R-O
unsigned word
1
40032 Service requests
maintenance register (see
list at chapter 10.3)
16 BIT
R-O
unsigned word
1