D-500 MK3 User Manual Firmware V-7.5
- 190 -
Modbus Slave Address:
may be set between 1 and 240
RS-485 Enable:
must be set to 1 (or checkbox enabled)
RS-485 Baud Rate:
selectable between 2400 and 115200 bauds. All devices in the same network must
use the same Baud Rate.
Selecting a higher baud rate will allow faster communication, but will reduce the communication distance.
Selecting a lower baud rate will increase the communication distance, but will cause slower response
times.
Typically 9600 bauds will allow 1200m distance with special balanced 120 ohms cable.
Modbus Slave Address:
may be set between 1 and 240. If only one unit is available in the same IP
address, it is advised to keep the default address (1).
Ethernet Enable:
This parameter should be set to 1 (or checked) in order to enable the ethernet port.
Modbus TCP/IP Port:
The usual setting is 502. However the unit is able to work on any port address.
User IP Mask:
There are 3 mask registers available. The use of the registers are emphasized in the
D500 User Manual. Please set the first mask as 255.255.255.0 for the proper operation.
Ethernet Network IP:
May be left as 0.0.0.0 for automatic address claim or set to a value in order to
claim a defined address.
Ethernet Gateway IP:
Should be set in accordance with your local switch configuration.
Ethernet Subnet Mask:
Should be set in accordance with your local switch configuration.
16bit variables:
These variables are stored in a single register. Bit_0 denotes the LSB and bit 15
denotes the MSB.
32 bit variables:
These variables are stored in 2 consecutive registers. The high order 16 bits are in the
first register and the low order 16 bits are in the second register
Bit arrays:
Arrays larger than 16 bits are stored in multiple registers. The LSB of the first register is bit_0.
The MSB of the first register is bit_15. The LSB of the second register is bit_16. The MSB of the second
register is bit_31, and so on.
35.3. DATA FORMATS
35.2. PARAMETERS REQUIRED FOR MODBUS-TCP/IP VIA ETHERNET
35.1. PARAMETERS REQUIRED FOR RS-485 MODBUS OPERATION
Содержание D-500 MK3
Страница 40: ...D 500 MK3 User Manual Firmware V 7 5 40 5 3 3 PHASE 3 WIRE DELTA 5 2 3 PHASE 4 WIRE STAR ...
Страница 41: ...D 500 MK3 User Manual Firmware V 7 5 41 5 4 3 PHASE 4 WIRE DELTA 5 5 3 PHASE 3 WIRE DELTA 2 CT L1 L2 ...
Страница 43: ...D 500 MK3 User Manual Firmware V 7 5 43 5 9 1 PHASE 2 WIRE 5 8 2 PHASE 3 WIRE DELTA 2 CTs L1 L3 ...
Страница 53: ...D 500 MK3 User Manual Firmware V 7 5 53 7 1 GENSET SYNCHRONIZATION FUNCTIONALITY 7 CONNECTION DIAGRAMS ...
Страница 54: ...D 500 MK3 User Manual Firmware V 7 5 54 7 2 MAINS SYNCHRONIZATION FUNCTIONALITY ...
Страница 55: ...D 500 MK3 User Manual Firmware V 7 5 55 7 3 SINGLE GENSET PARALLEL WITH MAINS FUNCT ...
Страница 56: ...D 500 MK3 User Manual Firmware V 7 5 56 7 4 AMF FUNCTIONALITY ...
Страница 57: ...D 500 MK3 User Manual Firmware V 7 5 57 7 5 ATS FUNCTIONALITY ...
Страница 58: ...D 500 MK3 User Manual Firmware V 7 5 58 7 6 REMOTE START FUNCTIONALITY ...
Страница 59: ...D 500 MK3 User Manual Firmware V 7 5 59 7 7 ENGINE CONTROL FUNCTIONALITY ...
Страница 60: ...D 500 MK3 User Manual Firmware V 7 5 60 7 8 REMOTE DISPLAY PANEL FUNCTIONALITY ...
Страница 72: ...D 500 MK3 User Manual Firmware V 7 5 72 ...