D-500 MK3 User Manual Firmware V-7.5
- 162 -
In this mode, the transfer will be made without interruption like the
Uninterrupted Transfer
mode. But the
load will be gradually transferred under
active and reactive power
control.
The Soft Transfer sequence starts like an Uninterrupted transfer. But when both contactors are activated,
the unit starts transferring the kW and kVAr load to the mains with a predefined ramp (
Active Power
Ramp, Reactive Power Ramp
). The duration of the load transfer sequence is controlled by the
Soft
Transfer Timer
.
The unit offers a comprehensive set of protection functions to detect quickly a mains failure during parallel
operation with mains. The protections are enabled after the timeout defined by the parameter
Parallel
Check Delay.
These protections will be explained with more detail in the following chapter.
If a
mains failure
occurs during parallel with mains operation, the mains contactor will immediately de-
energize, a general
Parallel Mains Fail
warning and a specific protection function warning will be
generated.
At the end of the
Soft Transfer Timer, the
load contactor will be released. If any alarm is encountered
during the
Soft Transfer
sequence, the controller will revert to the Interrupted transfer.
The controller has a set of programmable parameters to define the Soft Transfer operation. All
parameters used in Uninterrupted Transfer are also used in Soft Transfer. Additional parameters are:
Parameter Definition Description
Soft Transfer Enable
This parameter enables/disables the Soft Transfer feature.
Soft Transfer Timer
This is the time duration of the Soft Transfer. At the end of this timer one of
the contactors will release to terminate the parallel operation
Active Power Ramp
The load’s active power (kW) will be transferred to the mains with this rate.
Reactive Power
Ramp
The load’s reactive power (kVAr) will be transferred to the mains with this rate.
Ramp On High Limit
This parameter defines high limit of soft transferring from busbar to mains.
Ramp Off Low Limit
This parameter defines low limit of soft transferring from busbar to mains.
Parallel Check Delay
This is the delay after the mains contactor is energized (for parallel to mains)
and before the protections for mains failure are enabled.
29.3. SOFT TRANSFER
Содержание D-500 MK3
Страница 40: ...D 500 MK3 User Manual Firmware V 7 5 40 5 3 3 PHASE 3 WIRE DELTA 5 2 3 PHASE 4 WIRE STAR ...
Страница 41: ...D 500 MK3 User Manual Firmware V 7 5 41 5 4 3 PHASE 4 WIRE DELTA 5 5 3 PHASE 3 WIRE DELTA 2 CT L1 L2 ...
Страница 43: ...D 500 MK3 User Manual Firmware V 7 5 43 5 9 1 PHASE 2 WIRE 5 8 2 PHASE 3 WIRE DELTA 2 CTs L1 L3 ...
Страница 53: ...D 500 MK3 User Manual Firmware V 7 5 53 7 1 GENSET SYNCHRONIZATION FUNCTIONALITY 7 CONNECTION DIAGRAMS ...
Страница 54: ...D 500 MK3 User Manual Firmware V 7 5 54 7 2 MAINS SYNCHRONIZATION FUNCTIONALITY ...
Страница 55: ...D 500 MK3 User Manual Firmware V 7 5 55 7 3 SINGLE GENSET PARALLEL WITH MAINS FUNCT ...
Страница 56: ...D 500 MK3 User Manual Firmware V 7 5 56 7 4 AMF FUNCTIONALITY ...
Страница 57: ...D 500 MK3 User Manual Firmware V 7 5 57 7 5 ATS FUNCTIONALITY ...
Страница 58: ...D 500 MK3 User Manual Firmware V 7 5 58 7 6 REMOTE START FUNCTIONALITY ...
Страница 59: ...D 500 MK3 User Manual Firmware V 7 5 59 7 7 ENGINE CONTROL FUNCTIONALITY ...
Страница 60: ...D 500 MK3 User Manual Firmware V 7 5 60 7 8 REMOTE DISPLAY PANEL FUNCTIONALITY ...
Страница 72: ...D 500 MK3 User Manual Firmware V 7 5 72 ...